Design Guide › Coils
Cyclotron coils design rules
126 of the guide’s 1878 rules carry the coils tag.
Rules for the exciting coils: ampere-turn budgets, conductor sizing, current density and cooling, insulation, and the resistance-versus-power trades that set the magnet supply.
Each rule keeps its formula where the source gives one, a verbatim quote, a page-level
citation, and a stable identifier (dg-NNNN) that resolves here and on the
all-in-one guide. Where an editorial note says
“the reference machine”, its parameters are on the
guide’s front page.
By applicability level: level 2 (64) · level 3 (54) · level 4 (7) · level 5 (1) — levels rank breadth, never license to skip (method). Related domains, by shared rules: Magnet (63), Fabrication (18), Safety (13), RF (12), Materials (10). To combine tags or levels, open this domain in the filterable view.
Verify before use. Every rule here is a source extract in the vocabulary of the editorial methodology — faithful to its cited page, not an independently validated engineering requirement. Re-read any rule that drives a real design decision at the cited page before committing metal, money, or high voltage to it. The editorial note under each quote is this site’s extrapolation to a tabletop machine, not something the source said: an editor’s judgement, audited for overreach, never a citation.
-
The gap field follows B = mu0*Ni/g while the iron is well below saturation; at higher excitation the observed field falls short of the ideal - Livingston & Blewett's example delivered 0.73 of the prediction at 18 kilogauss - as iron reluctance and leakage grow.
B = K*mu0*Ni/g; K -> 1 at low excitation, measured 0.73 at 18 kG on their magnet; 10 kG across a 10 cm gap: 7.95e4 A-turns idealSource quote & editorial note
To produce a field B of 1 weber/m2 (10 kilogauss) in a gap of 10 cm length, the number of ampere-turns required is 7.95 x 10^4 ... At 18 kilogauss ... the observed value of B is 0.73 of that predicted.
Livingston & Blewett, Particle Accelerators (1962) — p. 258-260
Editorial note, tabletop extrapolation: At the reference machine's 5.9 kG the ideal formula is a good first estimate (~1.7e4 ampere-turns across its 3.6 cm gap) before iron reluctance and leakage add their share - FEMM closes that gap. Field headroom is cheap while the iron stays unsaturated and expensive after; where the knee sits is a property of the specific circuit, not a universal 10 kG line.
-
A 'dished' (saucer-shaped) median plane indicates asymmetric magnet or foundation iron, asymmetrically located coils, or a shorted turn; MIT flattened one case by paralleling an external resistor across one coil layer to trim its current.
Source quote & editorial note
a common phenomenon ... is to find the median plane dished into a shallow saucer shape caused by asymmetries in the magnet iron or of the reinforcing iron in the foundations. A similar shape will result if the coils are not located symmetrically or if there is a shorted turn. ... At MIT such a 'dished' median plane was corrected by connecting an external resistor in parallel with one of the coil layers, which reduced the current in this layer and in this case had the effect of flattening the median plane.
Livingston & Blewett, Particle Accelerators (1962) — p. 288
Editorial note, tabletop extrapolation: Rebar in the floor or a nearby steel bench can dish an H-frame tabletop field; remove or symmetrize nearby steel first where practical, then trim electrically (a rated shunt across one accessible layer, as MIT did) rather than re-machining.
-
Plan roughly 20 kW of DC coil power - water-cooled hollow copper tubing on a 2-ton mild-steel core, 33-inch-diameter coils, poles tapered from 12-inch stems to 10-inch faces, 17,000 gauss - as the Iowa State 1.5 MeV undergraduate cyclotron's magnet budget. [2026-09-06 re-read note: the paper gives no pole-gap figure anywhere - its only gap dimensions are the dee gap (1.5 cm) and dee height (2.4 cm), and Figure 5 is explicitly not to scale.]
20 kW dc into water-cooled hollow-copper coils; 33 in coil diameter; 2-ton mild-steel core (Iowa State 1.5 MeV machine)Source quote & editorial note
The magnet consists of coils of hollow copper tubing wound on a two-ton core of mild steel. ... capable of producing a very uniform 17,000 gauss field ... tapered from 12-inch pole stems to 10-inch pole faces.
McGuire, The Iowa State University 1.5 MeV Undergraduate Cyclotron (1961) — p. PDF 7 (printed 479) carries the quoted 20 kW sentence; the magnet paragraph is on PDF 5 (printed 477) and Table 1 on PDF 9 (printed 481)
Editorial note, tabletop extrapolation: Sets the scale of the jump from the reference machine's 0.59 T solid-tubing magnet toward a 1.5-1.7 T machine: at multi-kilowatt dissipation, hollow conductor with water flow is the usual regime (dg-092). The exact power for a next machine depends on its actual gap, field and copper budget - the magnet-power calculator sizes it, this precedent scales it.
-
Size the coil from NI = B*g/mu0 as the first cut: 1.6 T across their 2.13-in gap computes to ~69 kA-turns, and they built 720 turns at 110 A (~79 kA-turns) - roughly 15% above the ideal figure, margin that real iron reluctance and leakage consume.
NI = B*g/mu0 (ideal gap-only first cut); their example: 68.9 kA-turns ideal, 79.2 kA-turns builtSource quote & editorial note
we used the basic equation for an electromagnet... we decided a 2.13'' gap a reasonable size... we then concluded that we needed 720 turns to reach 1.6T.
Heuer & Baumgartner, Design of a 2 MeV Cyclotron (2009) — p. 32
Editorial note, tabletop extrapolation: The same sizing equation the reference machine's magnet obeys (its 538 turns are that build's own number, not this source's). The gap-only formula is the floor; the source's ~15% surplus is a realistic allowance for what it omits, and FEMM confirms the actual requirement (dg-016).
-
Dipole excitation per gap is NI = B*g/mu0, valid when iron path reluctance lambda/mu is negligible versus the gap; the exact form B_air = mu0*NI/(g + lambda/mu) shows when iron nearing saturation starts stealing amp-turns.
B_air = mu0*NI/(g + lambda/mu) ~ mu0*NI/gSource quote & editorial note
Bair = mu0 NI / (g + lambda/mu); ... Approximation ignoring iron reluctance (lambda/mu << g): NI = B g /mu0
Marks, Conventional Magnets for Accelerators — CAS lecture (2004) — p. 25
Editorial note, tabletop extrapolation: The correction term is one contributor that bends the excitation curve at high current: comparing measured B-vs-I against the lumped formula flags when the iron starts stealing amp-turns - attributing the bend among saturation, leakage and fringing then belongs to FEMM, which the lumped model cannot do.
-
Estimate magnet stored energy as U = B^2/(2*mu0) * (gap volume) and coil inductance as L_coil = 2U/I^2; the ramping voltage needed is V ~ B0*N*a*L/dt with L the magnet length (the source's own symbol), so turn count N is the only free knob for matching a power supply once field, gap, and ramp time are fixed.
U = B^2/(2*mu0)*V_gap; L_coil = 2U/I^2; V = B0*N*a*L/dt + I*R (a = pole width, L = magnet length)Source quote & editorial note
Given the field = B0, pole width = a, Magnet Length = L and ramp time dt, the only design option available for changing the voltage is the number of turns, N.
Editorial note, tabletop extrapolation: Quick check on a next machine's supply matching: stored energy in a 10-inch, 1 T, 5 cm gap magnet is about 1 kJ from the gap alone (B^2/(2*mu0) x volume; fringe fields add more), and turn count trades current for voltage against whatever surplus supply the builder finds.
-
Define coil regions by a closed polygon with cur = total ampere-turns (sign sets flux direction: negative current in the right-hand coil gives positive flux on the horizontal centerline); every region polygon must close, first point equal to last.
$reg mat=1 cur=-20000$ for a 20,000 A-turn coil block; all $po ... $ region polygons must closeSource quote & editorial note
Note that all regions must close, that is the first and last coordinates are equal ... Negative currents in the right hand coil gives positive flux on the horizontal centerline.
Editorial note, tabletop extrapolation: The two mistakes that make a first POISSON run fail; also shows amp-turns (not turns and amps separately) are what the model needs.
-
Compute dipole excitation as NI = B*h/mu0 divided by an efficiency of about 0.98 - a well-designed iron yoke eats only ~2% of the MMF.
NI = B0*h/(mu0*eta), eta ~ 0.98Source quote & editorial note
efficiency ~ 0.98 For magnets with well designed yokes.
Tanabe, Iron Dominated Electromagnets, Lecture 6: Excitation, Coil Design, System Design and Water Flow (2005) — p. 4-6, 12
Editorial note, tabletop extrapolation: Lets the builder size a next machine's amp-turns by hand before any FEA - with the ~2% read correctly: it is the yoke's MMF consumption in a well-designed magnet, not the accuracy of the estimate. Saturation, the real B-H curve, leakage and geometry can move the answer by far more than 2%, which is what the FEMM pass is for.
-
Never route the magnet's electrical bus so the supply conductors form a loop around the beam path - the loop makes a stray solenoidal field that rotates the beam; run feed and return conductors close together.
Source quote & editorial note
The electrical bussing connection creates a loop around the beam line, resulting in a small solenoidal field... the in and out conductors should be placed close to each other.
Editorial note, tabletop extrapolation: Cheap to get right on a next machine: dress the coil leads as a twisted/adjacent pair and keep supply cables from encircling the chamber.
-
Do first-pass cyclotron magnet numbers analytically with the lecture's formula set: average field <B> = alpha*B_hill + (1-alpha)*B_valley (alpha = pole azimuthal fraction), flutter F = alpha(1-alpha)(B_hill-B_valley)^2/<B>^2, total flux Phi = B_hill*S_poles (a hard-edge estimate that neglects the valley contribution), NI from Ampere's law, and coil cooling dT(C) = 60*P(kW)/(4.19*N(l/min)).
dT(C) = 60*P(kW)/(4.19*N(l/min)); F = alpha(1-alpha)(Bh-Bv)^2/<B>^2Source quote & editorial note
coil cooling estimation: dT(C) = 60*P(kW)/(4.19*N(l/min))
Zaremba, Magnets for Cyclotrons (2005) — p. 30-32
Editorial note, tabletop extrapolation: The cooling formula is immediately usable: a next machine's 5 kW coil at 4 L/min runs ~18 C water rise; the flutter formulas matter only if the builder adds sector (AVF) pole faces.
-
Compute the required excitation directly from the gap: NI per pole = B*h/(2*eta*mu0), with efficiency eta typically 99% for a well-designed iron circuit - pole area does not enter the ideal term - and the source's own warning kept: the equation is approximate, neglecting fringe fields and iron saturation.
NI_per_pole = B*h/(2*eta*mu0); eta ~ 0.99; mu0 = 4*pi*1e-7Source quote & editorial note
where h is the magnet gap height in [m] ... eta is the efficiency (typically 99%), mu_0 is the permeability of free space ... Note that Eq. (5) is only approximate and neglects fringe fields and iron saturation.
Editorial note, tabletop extrapolation: First-cut sizing for a next machine: at a 2 cm gap and 1.0 T, ~8000 A-turns per pole sets conductor and current-density scale before any FEMM run - the floor that FEMM then corrects for fringe and saturation.
-
Estimate stored energy (hence inductance L = 2U/I^2 and supply voltage) for a simple gap magnet as U = B^2/(2mu0) * (V_gap + 2*V_coil/6 + V_yoke/mu_r).
U_magnet = B^2/(2 mu0)*(V_gap + 2*V_coil/6 + V_yoke/mu_r); energy-equivalent L = 2U/I^2 (valid for a near-linear circuit - near saturation the ramp voltage follows d(flux linkage)/dt, not this L); V_tot = R*I + L*dI/dtSource quote & editorial note
U_magnet = U_gap + 2 U_coil + U_yoke = B^2/(2 mu_0) (V_gap + 2 V_coil/6 + (1/mu_r) V_yoke)
Editorial note, tabletop extrapolation: Tells you the inductance scale and therefore how fast a bench supply can ramp the magnet and how big the flyback/dump protection must be (dg-218) - computing the protection against the worst-case inductance across the operating range, not the single linear figure.
-
Estimate the mean turn length as l_avg = pole perimeter + 8 x (clearance between pole and coil) + 4 x coil width - the quoted formula; the lecture's sanity band 2.5*l_iron < l_avg < 3*l_iron (l_iron the iron core length) is its companion check for racetrack geometry (scan re-read queued).
l_avg = pole perimeter + 8*clearance + 4*coil width; 2.5 l_iron < l_avg < 3 l_ironSource quote & editorial note
l_avg = pole perimeter + 8 x clearance between pole and coil + 4 x coil width
Editorial note, tabletop extrapolation: Gives copper length, hence resistance and power, straight off a sketch - exactly what a garage builder needs before ordering tubing.
-
Pick current density from the cooling method and coil geometry: at most 1 A/mm^2 for voluminous coils almost entirely enclosed in the yoke, up to ~2 A/mm^2 only for small thin well-exposed air-cooled coils, and up to ~10 A/mm^2 as the typical upper end for direct water-cooled hollow conductor - higher is possible but at the cost of reliability.
air (bulky, enclosed): j <= 1 A/mm^2; air (small, thin): j < 2 A/mm^2; water-cooled: j up to ~10 A/mm^2 (typical upper end)Source quote & editorial note
the maximum current density for voluminous coils which are almost entirely enclosed in the magnet yoke should not exceed 1 A/mm2 ... The current density in direct water-cooled coils can be typically as high as 10 A/mm2.
Zickler, Basic Design and Engineering of Normal-Conducting, Iron-Dominated Electromagnets — arXiv:1103.1119 (2010) — p. 28-29, 31
Editorial note, tabletop extrapolation: The reference machine's 538-turn solid copper tubing coils sit in the air-cooled regime; unless they qualify as small and thin enough to shed heat (the source's 2 A/mm^2 case), the quoted limit for enclosed coils is 1 A/mm^2 - going higher means hollow conductor with water flow.
-
Design water cooling to keep coolant velocity turbulent but below 5 m/s (Re > 4000), coil surface below 60 C, and water temperature rise <= 30 C from a 30 C inlet, with 0.1-1.0 MPa (1-10 bar) available pressure drop.
u_avg <= 5 m/s; Re > 4000; dT <= 30 C; T_surface < 60 C; dp = 0.1-1.0 MPaSource quote & editorial note
The velocity of the cooling medium ... should be sufficiently high to guarantee a turbulent flow but low enough (u_avg <= 5 m/s) to avoid erosion and vibration. A maximum permitted temperature of less than 60 C on the coil surfaces was found to be good practice.
Editorial note, tabletop extrapolation: Hard numbers for a home chilled-water loop as DESIGN limits, not damage cliffs: hold velocity under ~5 m/s (erosion and vibration risk grow beyond it), coil surfaces under 60 C (insulation aging accelerates with temperature), and note the arithmetic - a 30 C inlet plus 30 C rise means up to 60 C outlet water, consistent with the surface limit but tight in a hot garage: derate for your ambient.
-
Use the closed-form water-cooling recipe in the source's units throughout: flow Q[l/s] = 2.388e-4 * P/dT, temperature rise dT = 3.04e-7 * P/(u_avg d^2), and required bore d = 5.59e-3 * (P/(dT*Kw))^0.368 * (l/dp)^0.21, with Kw as defined in the source.
Q = 2.388e-4 P/dT; dT = 3.04e-7 P/(u d^2); d = 5.59e-3 (P/(dT Kw))^0.368 (l/dp)^0.21; u_avg = 0.3926 d^0.714 (dp/l)^0.57 - coefficient-based, unit-specific: convert every input to the source's units before useSource quote & editorial note
Q_water = 2.388 x 10^-4 P/dT ... d = 5.59 x 10^-3 (P/(dT Kw))^0.368 (l/dp)^0.21
Editorial note, tabletop extrapolation: Lets the builder compute the hollow-conductor bore and pump requirement for a next machine's 5-20 kW magnet with a spreadsheet, no CFD - provided every input is converted to the source's units first: a bar-for-pascal slip in the pressure drop moves the bore answer far more than the recipe's real margin.
-
Compute dipole excitation as NI = B*h/(eta*mu0) with magnet efficiency eta ~= 98% for a well-designed unsaturated yoke (the iron path costs only ~1-2% extra ampere-turns when mu_iron >= 1000 and L_iron <= 10h).
NI_dipole = B*h/(eta*mu0), eta ~ 0.98Source quote & editorial note
NI_dipole = Bh/(eta*mu0), where the magnet efficiency, eta... The magnet efficiency for a well designed yoke is eta >= 98%.
Tanabe, Iron Dominated Electromagnets: Design, Fabrication, Assembly and Measurements — SLAC-R-754 (2005) — p. 116-117, 129
Editorial note, tabletop extrapolation: One-line check of the reference machine's 538 turns: at 0.59 T and its gap the formula predicts the required current within a couple percent if the H-frame iron is unsaturated. A measured efficiency well below the formula's ~98% says the model is missing something - saturation, leakage, a parasitic joint gap, or a wrong effective-gap value - and FEMM sorts out which.
-
First-order coil sizing: producing 1 T across a 2 cm gap requires ~16 kA-turns (e.g. 160 turns at 100 A); for a given supply and winding, gap field is inversely proportional to pole spacing.
NI = B*g/mu0; 1 T x 0.02 m -> 1.6e4 A-turnsSource quote & editorial note
production of a field of 1 T in a gap with a 0.02 m spacing requires 16-kA turns (160 turns of wire if a 100-A supply is available).
Humphries, Principles of Charged Particle Acceleration (1986) — p. 111
Editorial note, tabletop extrapolation: Numerically the builder's own worked example: 538 turns at ~30 A across the reference machine's 1.42-in (3.6 cm) gap predicts ~0.56 T from the ideal gap formula - an upper bound, because real iron reluctance and leakage only subtract from it. The measured shortfall from ideal maps those losses; FEMM attributes them.
-
Compute magnet excitation from NI = 2.02 x B(gauss) x gap(inches) - the ideal air-gap MMF in historical units (NI = B*g/mu0).
NI (ampere-turns) = 2.02 x gauss x inches of gapSource quote & editorial note
Ampere-Turns = 2.02 x gauss x inches gap
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 13
Editorial note, tabletop extrapolation: Directly applicable: 5900 G across a 2-inch gap needs ~24,000 ampere-turns as the ideal floor, with iron reluctance and leakage added on top (dg-016, dg-036). Leakage multiplies the FLUX the iron must carry - that sizes the yoke - not the gap MMF this formula computes.
-
Watch for adding-type trim coil configurations like the reference thesis's modelled cases, where B rises with radius out to ~5 cm: that produces a NEGATIVE field index (down to -0.1 in those models) and axial defocusing.
B increasing to r ~ 5 cm -> n < 0 (down to -0.1 in the modelled cases)Source quote & editorial note
the magnetic field actually increases in magnitude out to around r = 5 cm at which point it begins decreasing again. This is problematic because it yields a negative field index
Morrow, Focusing in the Houghton College Cyclotron — Houghton College thesis (2015) — p. 51-53
Editorial note, tabletop extrapolation: A concrete trap when adding iron or coils near the center of an 8-inch pole: check the sign of dB/dr over the whole usable orbit range, not just at the edge - the 5 cm crossover and the -0.1 index are that geometry's numbers, not general thresholds.
-
Do not expect a bucking-coil fix to rescue weak focusing cheaply: in the reference thesis's modelled geometry, bucking coils moved the n = 0.2 radius outward by only ~0.2 cm while cutting peak field from 1.27 T to 1.07 T - a 15.7% drop the source rounds to '~20%' - and the modification was judged insufficient.
dr(n=0.2) = +0.2 cm for dB: 1.27 T -> 1.07 T (a 15.7% decrease; the source says ~20%); energy scales with (B r)^2 of the final orbit, so trading field for a marginal radius gain losesSource quote & editorial note
the difference in radius is minimal - about 0.2 cm - and comes at the steep cost of a ~20% reduction in maximum magnetic field from 1.27 T to 1.07 T. As such, this modification was considered insufficient.
Morrow, Focusing in the Houghton College Cyclotron — Houghton College thesis (2015) — p. 53-54
Editorial note, tabletop extrapolation: Saves a next machine's builder from spending months on one class of trim-coil fix inside a small gap (they also steal gap height) - but this is one modelled geometry: evaluate any other trim-coil design from its full B(r) map and orbit dynamics.
-
Budget cooling water across subsystems explicitly - the Houghton thesis's own bookkeeping: the 15 cm magnet wanted 6.1 L/min at 70 A, but the chiller could spare only 3.0 L/min after the diffusion pump's 0.8, capping operation at 50 A / 1.1 T. The source attributes the field limit to both cooling and the power supply ('the maximum field is limited by available water cooling and the power supply'); the thesis's own arithmetic makes cooling the binding constraint at 70 A.
GMW 3473-70: 70 A needs 6.1 L/min; chiller 3.8 L/min total -> limited to 50 A, 1.1 T at 3.85 cm gapSource quote & editorial note
A Haskris H-4057 water chiller, capable of 3.8 L/min (1.0 gpm) ... Since the diffusion pump requires at least 0.8 L/min, the maximum that can be supplied to the magnet is 3.0 L/min ... the magnet requires 6.1 L/min
Loucks, Initial Results from the Houghton College Cyclotron — Houghton College thesis (2007) — p. PDF p.36 = printed p.36 (Loucks thesis Sec. 3.2 Magnet); the cited '35-36' range is correct, all figures are on 36
Editorial note, tabletop extrapolation: Do the L/min bookkeeping for the whole next machine (magnet + diffusion/turbo + RF amp) before buying a chiller; the cooling loop is a first-class design constraint, not an afterthought.
-
A 1.2 T tabletop cyclotron design point: 15 cm flat pole faces with the chamber in place giving a 3.81 cm pole-tip separation, 1.28 T at 70 A, water cooled at 18 C and 0.8 gallon/min at 50 A.
15 cm poles, gap 3.81 cm, 1.28 T at 70 A (1.16 T at 50 A); cooling 18 C water at 0.8 gpmSource quote & editorial note
With the chamber in place, the separation between the pole tips is 3.81 cm, giving a maximum magnetic field of 1.28 T at 70 A ... requiring 18 C water flowing at 0.8 gallons per minute (at 50A)
Editorial note, tabletop extrapolation: A purchasable-magnet benchmark almost exactly at the reference machine's scale. The 0.8 gpm is a flow figure, not a chiller spec: size the chiller from coil dissipation and allowable temperature rise (P = flow x heat capacity x dT - the magnet-power calculator's territory), with the flow number as the plumbing constraint it is.
-
Power the upper and lower coils from independent supplies so a deliberate top/bottom ampere-turn imbalance can shift the beam's vertical equilibrium (accelerating) plane onto the geometric midplane of the dee.
Source quote & editorial note
The magnet's upper and lower coils are independently energized enabling an intentional axial field imbalance so as to vertically shift the accelerating plane.
Koeth, Undergraduate Education with the Rutgers 12-Inch Cyclotron (2015) — p. 2
Editorial note, tabletop extrapolation: Cheap beam-height trim for a next machine: two supplies, or a properly rated current-trim circuit on one coil, instead of re-machining anything - verify the result with a field or beam measurement, since unequal excitation perturbs the midplane symmetry it exploits.
Cited in: Beam Dynamics: An Interactive Laboratory
-
Reach for the iron before the copper when shaping a warm magnet's field: trim coils increase the gap and are 'very weak except in superconducting machines' - and even then, model before implementing (both quoted); iron shaping carries the flip side the lecture tabulates - effective and cheap but non-linear and fixed once cut (comparison rows: scan re-read queued).
Source quote & editorial note
Trim coils increase the gap ... Very weak except in superconducting machines ... Model it before implementing it to avoid unexpected effects
Beeckman, Cyclotron Magnets — ECPM37 lecture, Groningen (2009) — p. 33, 47
Editorial note, tabletop extrapolation: Settles the shim-vs-trim-coil question for a small warm magnet the way the Houghton thesis found empirically: iron wins for the main profile. A weak trim coil can still earn a place for fine, reversible adjustment where the gap budget allows one.
-
Field in the gap of an iron-dominated magnet is B = mu0*n*I/h - proportional to total ampere-turns, inversely proportional to gap, and independent of pole area; so minimize the reluctance of the iron path so the ampere-turns are spent on the gap.
B = mu0 n I / h (h = gap height)Source quote & editorial note
the field B = mu0 nI/h is proportional to the total current in the solenoid, is inversely proportional to the magnetic gap and is independent on the pole surface, a rather counter-intuitive fact to most people.
Beeckman, Cyclotron Magnets — ECPM37 lecture, Groningen (2009) — p. 70-71
Editorial note, tabletop extrapolation: The core sizing identity for a home magnet, in its regime (unsaturated iron, h the total effective gap): field follows ampere-turns over gap, and bigger poles alone buy nothing. Shaving the gap buys field at the price of chamber, dee and beam clearance (dg-163's trade) - cheap, not free.
-
Wind a small auxiliary coil on each pole (86-inch: 65 turns, up to 75 A) to steer the beam onto the magnetic median plane with a controllable field asymmetry.
86-inch control coils: 65 turns of #6 wire per pole, dc supply to 75 ASource quote & editorial note
By means of auxiliary coils wound on the pole pieces it is possible to control the position of the beam with respect to the median plane of the tank. The coils consist of 65 turns of #6 wire wound on each pole piece. A dc power supply provides up to 75 amperes
Livingston & Boch, The Oak Ridge 86-Inch Cyclotron — ORNL-1196, OSTI 4357145 (1952) — p. 35
Editorial note, tabletop extrapolation: Cheap and direct for a next machine: an auxiliary winding on the poles gives a vertical-centering knob instead of mechanical re-shimming - size its ampere-turns from the field asymmetry the orbit calculation asks for (the 86-inch used up to ~4900 A-turns; a small machine needs proportionately less, but compute it), with a reversible supply and thermal check.
Cited in: Beam Dynamics: An Interactive Laboratory
-
For coil power, dissipation is inversely proportional to conductor volume, so choose power first and volume follows; keep packing ratio above 0.5 and size cooling water as q(gpm) = 6.82 x U(kW) / dT(degF).
P = rho*(NI)^2*l_turn^2/V_Cu (V_Cu = copper volume; with gross coil volume multiply the denominator by packing factor f); packing ratio > 0.5; q(gpm) = 6.82*U(kW)/dT(degF)Source quote & editorial note
power varies inversely with volume of conductor, so to a first approximation it can be chosen at will ... a well-designed coil will have a 'packing ratio' greater than 0.5.
Livingston & Blewett, Particle Accelerators (1962) — p. 273-277
Editorial note, tabletop extrapolation: If a next machine's coils run hot, more copper is a fix on equal footing with more cooling: doubling conductor volume halves dissipation at the same ampere-turns - paid for in coil size, weight and winding-window space.
-
Bond coils into solid resin (epoxy/polyester over glass or cotton tape) so conductors cannot move under magnetic forces; turn-to-turn resin-glass insulation is good for >100 V/mil, but use mica for the higher voltage-to-ground insulation.
resin-impregnated glass/cotton: >100 V/mil (10-30 mil layers); tensile 1000-3000 psiSource quote & editorial note
The voltage breakdown strength of a resin-impregnated layer of glass cloth or cotton mesh is usually over 100 volts/mil ... necessary to utilize mica-sheet or mica-flake insulation to obtain the higher voltage-to-ground insulation.
Livingston & Blewett, Particle Accelerators (1962) — p. 278
Editorial note, tabletop extrapolation: Potting the reference machine's coils stops the slow insulation abrasion that coil hum causes. The >100 V/mil figure is the source's historical material datum, not an allowable design stress: size insulation from maximum turn-to-turn and coil-to-ground voltage with margin for voids, transients, creepage and temperature - the quote itself reserves voltage-to-ground duty for mica - and prove the finished coil with a hipot test rather than resting on the coupon number.
-
The ANL 60-inch maintained cooling water demineralized at conductivity 10 micromho or less with pH about 7, and held dee cooling-water temperature stable to 1 F or better for steady operation.
sigma <= 10 umho/cm, pH ~7, dee water dT stability <= 1 FSource quote & editorial note
The conductivity is maintained at 10 micromhos or less, with a pH of about seven. Dee system water temperature stability of 1 F or better is required for steady operation.
Ramler & Parker, The Argonne 60-Inch Cyclotron — ANL-5907 (1959) — p. 6
Editorial note, tabletop extrapolation: Two portable METHODS, not specs: monitor conductivity and pH on any hollow-conductor DI loop, and stabilize dee-water temperature if a next machine water-cools the dee (the RF tune walks with dee temperature). Set the actual limits from conductor material, voltage to ground, and measured RF drift, not from ANL's numbers.
-
Size the cooling plant with about 3x margin over normal load (ANL: 1000 kW capacity vs ~300 kW normal operating load).
plant capacity ~ 3x normal heat loadSource quote & editorial note
The circulating pumps and heat exchanger are sized to handle a 1000-kw heat load, with the normal operating load being about 300 kw.
Ramler & Parker, The Argonne 60-Inch Cyclotron — ANL-5907 (1959) — p. 6
Editorial note, tabletop extrapolation: For a next machine dissipating 1-5 kW, real margin over normal load is what makes long runs boring - ANL carried about 3x; pick your own factor from duty cycle, ambient conditions and fouling allowance rather than copying the ratio.
-
Cool the RF matching secondary coil with oil or deionized water: even minute thermal expansion of the copper changes its inductance, detuning the network - which, uncompensated at fixed drive frequency, typically drops the dee voltage.
Source quote & editorial note
It is necessary for the secondary coil to be cooled with oil or deionized water... because even minute thermal expansion of the copper can change the inductor's value.
Heuer & Baumgartner, Design of a 2 MeV Cyclotron (2009) — p. 23
Editorial note, tabletop extrapolation: Explains RF drift during long runs at the reference machine's power levels; cooling the tank coil stabilizes tune.
-
The source's water-cooled 1/4 in x 1/4 in hollow square copper conductor, properly cooled, safely carried about 120 A; they designed the magnet to run at 110 A for margin.
source rating: ~120 A when properly cooled; operated at 110 ASource quote & editorial note
When properly cooled, our 1/4''x1/4'' hollow copper conductor can safely carry up to 120A. Allowing a margin of safety, we designed our magnet to operate at 110A.
Heuer & Baumgartner, Design of a 2 MeV Cyclotron (2009) — p. 32
Editorial note, tabletop extrapolation: A conductor rating like this is conditional on the cooling that produced it - wall thickness, bore, flow, inlet temperature - so treat it as one documented data point for hollow-conductor coils, not a transferable ampacity. Rate a next machine's conductor from its own cooling calculation; the coil-geometry and magnet-power calculators cover the resistive side.
-
Wind coils as 'double pancakes' (two-layer sub-coils with both leads exiting the same side): the source states this winding gives a more uniform field than a simple spiral.
Source quote & editorial note
Using this type of winding allows for a more uniform field than a simple spiral winding.
Heuer & Baumgartner, Design of a 2 MeV Cyclotron (2009) — p. 32-33
Editorial note, tabletop extrapolation: A rebuild of the reference machine's 538 turns as potted double-pancakes with a cooling manifold is an attractive concept - as a design study: pancake count, potting, parallel water paths and repairability are engineering choices needing their own magnetic, hydraulic and thermal analyses, not properties the source's uniformity comparison confers.
-
One machine's thermal envelope as calibration: the source magnet reports a 173 F (78 C) maximum and normal operation at no more than 142 F (61 C).
source magnet: T_normal <= 142 F (61 C), T_max 173 F (78 C)Source quote & editorial note
Our magnet can achieve a maximum temperature of 173 oF and will normally operate at no more than 142 oF.
Heuer & Baumgartner, Design of a 2 MeV Cyclotron (2009) — p. 33
Editorial note, tabletop extrapolation: Set a next machine's potted-coil design point from the resin system's rated thermal class and a modeled or measured hotspot with margin for cooling failure - not from another magnet's numbers. Note 61 C at ordinary ambient is already a 36-41 C rise, looser than Tanabe's ~30 C-rise guidance for long potted-coil life.
-
Pick the number of turns N to match the power supply once NI is fixed by the field requirement: large-N/low-I gives cheap thin cables but higher voltage, small-N/high-I gives low voltage, better copper packing and bulky connections - and N also drags resistance, inductance, stored energy and cooling geometry along, so the supply match is the starting constraint, not the only one.
NI fixed; N chosen from supply V/I window (Diamond dipole example: 40 turns, 1500 A, 500 V circuit)Source quote & editorial note
The value of number of turns (N) is chosen to match power supply and interconnection impedances.
Marks, Conventional Magnets for Accelerators — CAS lecture (2004) — p. 35-36
Editorial note, tabletop extrapolation: The reference machine's 538 turns were set by its supply; for a next machine, pick the surplus supply first and wind N = NI_required/I_supply - then check voltage compliance, inductance (and its dump-path consequences, dg-218) and cooling before committing.
-
Power-distribution cables are generally limited to a current density of about 1.5-2 A/mm^2 - the source's benchmark for what conductors carry without engineered cooling.
j (power cables) < 1.5-2 A/mm^2 (source's general figure)Source quote & editorial note
Power distribution cables... are generally limited to a current density of <1.5 to 2 Amps/mm2.
Editorial note, tabletop extrapolation: An orientation point, not a coil rating: magnet coils differ from distribution cables in bundling, enclosure and heat path. The coil-specific limits are dg-092's - voluminous enclosed coils are held to 1 A/mm^2, and water cooling is what opens the range upward.
-
Choose water-cooled coil current density near the canonical j = 10 A/mm^2 (economic optimum in worked example was flatter, ~4 A/mm^2; the higher value trades operating cost for smaller, cheaper coils).
j_design ~ 10 A/mm^2 water-cooled (economic optimum ~4 A/mm^2)Source quote & editorial note
the optimum is flat and appears to be j=4 Amps/mm2. However, a higher design value (the canonical j=10 Amps/mm2 value) is generally chosen.
Editorial note, tabletop extrapolation: For a home machine the source's trade often runs toward the low end: hand-wound coils and metered power favor the ~4 A/mm^2 economic optimum, and the reference machine's tubing coil runs lower still. Window space and magnet size push the other way - which is why the canonical 10 exists - so do the two-line cost comparison for your own copper and power prices.
-
Compute coil water pressure drop with the Darcy-Weisbach relation P = 0.433*f*(L/d)*(v^2/2g), using the Darcy friction factor f = 64/Re for laminar flow (Re < 2000) and the smooth-tube turbulent solution for Re > 4000; design in the turbulent regime for good heat transfer.
P[psi] = 0.433*f*(L/d)*(v^2/2g); Re = v*d/nu; nu(water, 20 C) ~ 1.08e-5 ft^2/s (1.0e-6 m2/s); f = 64/Re (Re < 2000); avoid designing in the 2000-4000 transition bandSource quote & editorial note
f = 64/Re for laminar flow Re < 2000. For turbulent flow (Re>4000), the friction factor is gotten by solving a transcendental equation.
Editorial note, tabletop extrapolation: The straight-passage core of hydraulic sizing for any hollow-conductor or tubing-wound coil - add bends, fittings and manifold (minor) losses on top, and confirm with a flow test; the formula alone is the floor, not the whole recipe.
-
Water temperature rise through a coil is dT(C) = 3.8*P(kW)/q(gpm); design for <10 C rise, and never exceed ~30 C rise (with 20 C inlet) if you want long potted-coil life.
dT[C] = 3.8*P[kW]/q[gpm] - standard water heat-capacity arithmetic in US units, not from the quote; quoted targets: < 10 C desirable, < 30 C maximum (20 C inlet) for long potted-coil lifeSource quote & editorial note
Desirable temperature rise... < 10 deg. C. Maximum allowable temperature rise (assuming 20 deg. C. input water) < 30 deg. C for long potted coil life.
Editorial note, tabletop extrapolation: One-line flow-rate calculator: a 1 kW coil on a next machine needs ~0.4 gpm for a 10 C rise.
-
Keep cooling-water velocity below 15 ft/s in coil passages; above that, flow-induced vibration erodes the water channel over time.
v_water < 15 ft/s (4.6 m/s)Source quote & editorial note
For water velocities > 15 fps, flow vibration will be present resulting in long term erosion of water cooling passage.
Editorial note, tabletop extrapolation: The cited source's upper design guideline when sizing pump and passage diameter for a hollow-conductor coil; onset of vibration and erosion also depends on bend severity, passage geometry, material and water chemistry, so use a lower limit where conductor-manufacturer guidance or testing warrants.
-
Doubling the number of parallel water circuits cut required pressure drop by a factor of eight in the source's sizing (P ~ 1/Nw^3, valid when each circuit's length and flow both scale as 1/Nw at fixed passage diameter and friction factor): subdivide the coil rather than buy a bigger pump.
P ~ 1/Nw^3 under fixed d and f with length and flow per circuit ~ 1/Nw; recompute per branch with real lengths, Reynolds-dependent f and manifold lossesSource quote & editorial note
Pressure drop can be decreased by a factor of eight if the number of water circuits are doubled.
Editorial note, tabletop extrapolation: Argues for manifolded pancake sub-coils on a next machine instead of one long series water path through 538 turns.
-
Cooling-passage pressure drop falls dramatically with hole diameter - roughly as 1/d^5 in the fixed-flow, fixed-friction-factor turbulent approximation - so a slightly larger hole slashes pump requirements, and an undersized (out-of-tolerance) hole blows the hydraulic budget.
P ~ 1/d^5 (fixed volumetric flow, ~fixed Darcy f; laminar flow gives ~1/d^4)Source quote & editorial note
If the design hole diameter is increased, the required pressure drop is decreased dramatically. If the fabricated hole diameter is too small... pressure drop can increase substantially.
Editorial note, tabletop extrapolation: When choosing hollow conductor for a next machine, weigh bore against copper cross-section (a bigger hole raises electrical resistance) and flow-test each pancake before potting - the fabricated bore, not the drawing, sets the pressure drop.
-
Wind each water circuit from one continuous length of conductor - no splices buried in the potting (the quoted requirements) - with the lecture's companion QA practices: a chip-free winding area, and a pre-winding ball test blowing a ball of <= 80% of the cooling-hole diameter through the passage (per its coil-quality pages: scan re-read queued).
ball diameter <= 0.8 * cooling-hole diameterSource quote & editorial note
A single water circuit in a coil assembly should be wound from a single continuous length of conductor. Splices 'buried' within the potted insulation should not be allowed.
Editorial note, tabletop extrapolation: For a next machine wound from copper refrigeration tubing: buy one continuous coil per water circuit, keep the shop swarf away from the winding, and verify the bore is clear before the tubing is buried in the stack.
-
Impulse-test coils for intermittent turn-to-turn shorts during fabrication: pulse a capacitor into the coil and watch the ringdown on a shielded pickup loop, starting at ~10 V/turn and raising to 200 V/turn or 2 kV maximum - a healthy coil's waveform only scales in amplitude, while frequency/damping changes or 'hash' at the peak indicate a short. The test only works on a coil isolated from metallic surfaces: core eddy currents and iron permeability mask the expected electrical behavior once the coil is installed on the core. After potting, hipot to twice the operating voltage plus 1 kV with drainage current under 2 mA/kV.
impulse: 10 V/turn up to 200 V/turn or 2 kV; hipot: 2x operating voltage + 1 kV, leakage <= 2 mA/kVSource quote & editorial note
This test can only be performed on a coil isolated from metallic surfaces and will not work once the coil is installed on the core. ... the iron permeability will mask the expected behavior of the electrical circuit.
Tanabe, Iron Dominated Electromagnets, Lecture 9: Coil Fabrication, Testing and Electrical Safety (2005) — p. PDF p.18 (slide deck, unnumbered); procedure on PDF p.17, hipot/QA context pp.19-20
Editorial note, tabletop extrapolation: A pulse source, capacitor and scope let the builder screen the next machine's coils before they are trapped under the yoke - run the impulse test during fabrication, before the coil goes on the core, and photograph the low- and high-voltage waveforms as the baseline. Both tests put hazardous voltage on the coil: use rated, current-limited test gear, discharge and ground between steps, and keep others clear.
-
Measure actual coil water flow at the real supply pressure and water temperature rather than trusting handbook calculations - bends that are tight relative to the passage size add flow impedance the straight-pipe formulas miss.
Source quote & editorial note
Water flow calculations made for the preliminary design may be unreliable for a coil designed with many tight turns... due to the added flow impedance of tight radius turns.
Editorial note, tabletop extrapolation: A bucket-and-stopwatch flow test at operating pressure is the real spec for the reference machine's 538-turn tubing coil (many turns; check its bend radii against the passage size). Record water temperature - viscosity matters most if any branch runs laminar - and measure each parallel branch separately, since a total-flow test hides an imbalance.
-
Use non-conducting cooling water hoses at least 1 m long between manifold and coil to limit leakage current, make the water inlet fitting smaller than the outlet, and put the flow-interlock orifice on the return manifold.
hose length >= 1 m, non-conductingSource quote & editorial note
Water hoses should be at least one meter long and use nonconducting material to prevent current leakage from the magnet. The water “in” fittings should be smaller than the water “out” fittings ... If a flow interlock (orifice plate) is used, it should be attached to the return manifold.
Editorial note, tabletop extrapolation: The reference machine's water-cooled copper-tubing coil sits at supply potential; a meter of non-conducting hose per lead limits leakage current, and an interlock on the return detects a blocked circuit - cheap practices worth copying at home scale. They reduce specific risks; they are not shock protection as a whole, which still rests on earthing and supply-side protective devices.
-
Fit each coil water circuit with a thermal interlock switch (Klixon) set near 89 C, mounted on the water-return end of the current-carrying conductor via a hard-soldered block, wired to kill the power supply.
trip ~89 C, reset ~70 C, one interlock per water circuit, all in seriesSource quote & editorial note
The normal set-point of Klixons is about 89 C. It will generally reset at about 70 C ... One thermal interlock is installed on each water circuit ... All the interlocks on one magnet are connected in series. ... The Klixon is preferably mounted on the water return lead of the coil ... always mounted on the current carrying portion of the conductor ... mounted to a block hard-soldered to the conductor.
Editorial note, tabletop extrapolation: A thermal snap-switch soldered to the coil exit tube, wired in series with the supply enable, is cheap, high-value protection against cooking a winding on a lost-water event - alongside the flow interlock (dg-202), not instead of it. Set-point and switch rating are the designer's to verify against the winding's own insulation limit.
-
Insulate coils to scale (the source's ranges): inter-turn insulation 0.3-1.0 mm; ground insulation 0.5-3.0 mm depending on the applied voltage.
water-cooled (SS4.6.2): inter-turn 0.3-1.0 mm; ground 0.5-3.0 mm. Air-cooled companion (SS4.6.1, restored 2026-09-06): varnish 0.02-0.1 mm or half-lapped Kapton 0.1-0.2 mm inter-turn, fill factor 0.63 (round) to 0.8 (rectangular), ground 0.5-2 mm epoxy-impregnated glass tapeSource quote & editorial note
ordered blank or pre-impregnated with varnish (0.02 ≤ t ≤ 0.1 mm) or half-overlapped polyimide (Kapton®) tape (0.1 ≤ t ≤ 0.2 mm) ... a filling factor between 0.63 (round) to 0.8 (rectangular) can be obtained.
Zickler, Basic Design and Engineering of Normal-Conducting, Iron-Dominated Electromagnets — arXiv:1103.1119 (2010) — p. PDF 29 (printed 93) for the quoted sentence; PDF 28-29 (printed 92-93) for the varnish/Kapton/filling-factor figures
Editorial note, tabletop extrapolation: Sets expectations for how much winding window the insulation eats on a hand-wound 538-turn coil - then compute the actual packing factor from the chosen conductor's finished insulated dimensions and the real winding layout, since fill depends on shape, pattern and voids, not on insulation thickness alone.
-
Wind hollow conductor with a bending radius at least four times the conductor width: at three widths the source expects 3.6% keystoning - local cross-sectional distortion at the bend - and recommends four widths so the effect can be ignored.
R = 3A -> ~3.6% keystoning (local distortion, not cumulative per-bend growth); use R >= 4A for the source's rectangular hollow conductorSource quote & editorial note
For a bending radius of three times the conductor width we can expect a keystoning of 3.6% ... we can ignore the effect of keystoning by systematically choosing a bending radius four times larger than the conductor width.
Editorial note, tabletop extrapolation: For bending round copper tubing on a homemade coil the analogous risks are ovalization and bore pinch: use tube-specific minimum-bend-radius and ovality limits (diameter, wall, temper and tooling all matter), inspect or flow-test the formed passage, and watch the insulation at the bends.
-
Dimension the coil pack with cross-section A = N*I/(j*fc), an aspect ratio (height:width) between 1:1 and 1:2, and a packing factor fc of 0.6-0.8.
A = b*c = N*I/(j*fc) - the standard winding-window equation, correct with fc as the conductor-area fraction (not from the quote); quoted ranges: c:b between 1:1 and 1:2, fc = 0.6-0.8Source quote & editorial note
An aspect ratio of c:b between 1:1 and 1:2 should be chosen, and the packing factor fc somewhere between 0.6 and 0.8.
Editorial note, tabletop extrapolation: Turns the amp-turn number into an actual coil window size before you buy tubing or start winding.
-
Split coils into more parallel water circuits before enlarging the pump: pressure drop scales as 1/Kw^3 (doubling the number of circuits cuts dp by a factor of 8) and as 1/d^5 in channel diameter.
dp ~ 1/Kw^3; dp ~ 1/d^5Source quote & editorial note
This implies that for a given flow, the pressure drop is reduced by a factor of eight by doubling the number of cooling circuits.
Editorial note, tabletop extrapolation: Explains why splitting a big coil into 2 or 4 hydraulic circuits lets a garage chiller pump do the job - under the model's conditions: total flow and total conductor length fixed, circuits dividing both equally; then pressure drop falls as the cube of the circuit count. Confirm the friction regime still holds after the split.
-
Feed hollow-conductor coils with demineralized water at resistivity > 0.1 MOhm*m, pH 6-6.5, and dissolved oxygen below 0.1 ppm, with filters near the magnet; poor water quality eventually causes shorts and corrosion leaks.
rho > 0.1e6 Ohm*m; pH 6-6.5; O2 < 0.1 ppmSource quote & editorial note
Water resistivity higher than 0.1x10^6 Ohm m; pH-value between 6 and 6.5; dissolved oxygen below 0.1 ppm
Editorial note, tabletop extrapolation: If a next machine uses water-cooled coils at supply potential, ordinary tap water misses all three quoted limits. A deionizing cartridge loop is the standard way to hold resistivity, but the spec is three-dimensional - oxygen and pH need their own control - and the source pairs the water spec with filters near the magnet.
-
Convectively cooled power-distribution cables are limited to j <= 1.5 A/mm^2 - the source's figure for that service.
j_air <= 1.5 A/mm^2Source quote & editorial note
power distribution cables are convectively cooled and are limited to <= 1.5 Amps/mm2
Tanabe, Iron Dominated Electromagnets: Design, Fabrication, Assembly and Measurements — SLAC-R-754 (2005) — p. 128-129
Editorial note, tabletop extrapolation: For the reference machine's circuit: any leg - bus, jumper, lead - running above ~1.5 A/mm^2 without an engineered cooling path will run warm, so size leads generously. Above the line the options are any real cooling: water, forced air, conductive sinking, or intermittent duty with temperature monitoring (dg-220).
-
Use the source's normally-good current density j = 10 A/mm^2 for water-cooled magnet coils and a packing fraction of ~0.5 for small conductors; the lecture's first-pass sizing also takes average turn length ~3x the magnet core length.
j = 10 A/mm^2 (water-cooled); f ~ 0.5; l_ave ~ 3*L_magSource quote & editorial note
Normally, a good value for the current density is j = 10 Amps/mm2 for water cooled coils... The value of the packing fraction is typically f ~ 0.5 for small conductors.
Editorial note, tabletop extrapolation: Lets the builder size a next machine's coil cross-section on one sheet of paper: gross winding area ~ NI/(j*f) = NI/5 mm^2 for water-cooled copper - a first pass the thermal calculation then confirms, and the 10 A/mm^2 presumes genuine water cooling (dg-092's geometry conditions).
-
Design coil water circuits for turbulent flow (the lecture's Re >= 4000 criterion) but keep flow velocity <= 4 m/s to avoid vibration and erosion of the copper passage, and hold coil temperature rise dT <= 30 C to protect epoxy insulation - the lecture tightens toward ~15 C where field stability matters.
Re >= 4000; v <= 4 m/s; dT <= 30 C (15 C for stability)Source quote & editorial note
Flow velocity should be high enough so that the flow is fully turbulent, Re ≳ 4000... For synchrotron radiation accelerators where beam stability depends on temperature stability, ∆T ≲ 15°C.
Tanabe, Iron Dominated Electromagnets: Design, Fabrication, Assembly and Measurements — SLAC-R-754 (2005) — p. PDF pp. 134-135 = printed pp. 134-135 (chapter section 'Coil Cooling'), as cited
Editorial note, tabletop extrapolation: Direct water-cooling design window for a next machine's hollow-conductor coil; also warns that a lazy laminar-flow circuit cools far worse than the handbook film coefficient suggests.
-
Estimate the coil power-weight tradeoff with kW x tons = 0.118 x (mega-ampere-turns)^2 x (mean turn length in inches)^2 for copper: the product of dissipation and weight is fixed by NI and geometry, so more copper always buys less heat.
kW x tons(Cu) = 0.118 x (MA-turns)^2 x (mean turn length in inches)^2 - the squared length follows from P*M ~ (NI)^2*l^2 and matches the 0.118 coefficient; the quoted line's missing exponent is likely transcription (scan re-read queued)Source quote & editorial note
Kilowatt-Tons = (0.118)Cu (Mega-ampere turns)^2 (inches mean turn length)
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 13
Editorial note, tabletop extrapolation: Directly applicable trade study tool: the product of coil dissipation and coil weight is fixed by NI and geometry, so more copper always buys less heat.
-
Wind coils to an approximately rectangular (square-ish) cross section around the poles; a coil that is too flat or too tall intercepts more leakage flux and wastes turns.
Source quote & editorial note
The coils should be wound so that they occupy approximately a rectangular cross section around the poles ... Either too flat or too tall a coil intercepts more leakage flux and thus wastes turns.
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 3
Editorial note, tabletop extrapolation: Directly applicable guidance for a next machine's coil geometry.
-
Limit close-wound naturally air-cooled coils to 750 A/in^2 of conductor continuously, 1000 A/in^2 for intermittent runs.
J <= 750 A/in^2 (1.16 A/mm^2) continuous, air-cooled; <= 1000 A/in^2 intermittentSource quote & editorial note
operate close-wound naturally air-cooled coils at a current density not exceeding 750 amps per square inch of conductor area. For intermittent operation this may be raised to 1000 amps per sq. in.
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 3
Editorial note, tabletop extrapolation: Directly applicable thermal sizing for coils matching the quoted conditions - close-wound, naturally air-cooled: 750 A/in^2 continuous, 1000 intermittent. A different winding style (open spacing, forced air, tubing with internal flow) carries different limits - dg-092's geometry table is the map.
-
Favor large conductor cross-section and high current over many turns at high voltage; this simplifies both insulation and winding.
Source quote & editorial note
Most coil designs favor large conductor areas and correspondingly high amperages; this reduces total voltage and simplifies both the insulation and the winding problems.
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 3
Editorial note, tabletop extrapolation: Directly applicable when choosing wire gauge and supply for a next machine's coils.
-
Wouters: flat donuts of 1/16 in. copper sheet with 1/4 in. copper pipe soldered to the outer edges, interleaved between pancake windings as cooling plates - together with a large fan for general circulation - should operate steadily at about 1300 amps per square inch.
J ~ 1300 A/in^2 (2.0 A/mm^2) with interleaved water-cooled donut platesSource quote & editorial note
flat donuts of 1/16 in. copper sheet ... During operation cold water is run through this set of pipes; together with a large fan for general circulation, such coils should operate steadily at 1300 amps per sq. in.
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. PDF p.4 (printed -5-); comparative current-density framing on PDF p.3 (printed -4-)
Editorial note, tabletop extrapolation: A cheap construction to reach for when a next machine's pancake coils run hot: 1/16-inch copper donut plates with soldered edge tubing between pancakes. The 1300 A/in^2 is the historical design target for that geometry, not a number to adopt - recompute I^2R, water flow and temperature rise, the thermal path through the insulation, and solder and tube reliability, then measure winding temperature in operation. [Note revised 2026-08-23: earlier note called it a directly applicable upgrade that 'nearly doubles' allowable excitation.]
-
Beware thermal margins on hobby-scale coils: the 6-inch's 6000-turn #13-wire coils reached iron saturation (~20 kG) below 10 A but overheated in under an hour at that current.
6-in example: 6000 turns #13 DSC wire, ~20 kG at <10 A, <1 hr thermal limitSource quote & editorial note
These windings saturate the iron (~20 KG) at somewhat less than ten amperes; at this current the temperature becomes excessive in less than an hour
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 4
Editorial note, tabletop extrapolation: Directly applicable cautionary datum: quote coil ratings as (current, time-to-overheat) pairs, not just maximum field.
-
Never open the magnet coil circuit at high current without surge protection (thyrite resistor or electrolytic dump tank) across the coil.
Source quote & editorial note
The magnet coil circuit must never be broken at high currents, of course, unless adequate surge protection is provided.
Wouters, General Recommendations for Design of Small Cyclotrons — UCRL-476 (1949) — p. 5
Editorial note, tabletop extrapolation: Directly applicable: any magnet coil whose stored energy exceeds a few joules needs a dump path across the winding - freewheel diode, varistor, or resistor - rated for the coil's stored energy, peak current and clamp voltage. Without one, opening the circuit at current can arc the switchgear.
-
Size the Dee tank circuit from the Dee capacitance: on the cited machine ~76 pF of Dee against a 0.87 uH secondary resonates up to 19.5 MHz (411 keV protons at its 1.28 T maximum field), with both inductors wound from 1/4 inch copper tubing coaxially - 6 cm diameter primary outside a 4 cm secondary - and coupling set by swapping primaries of different turn counts.
cited machine: C_dee ~ 76 pF, L >= 0.87 uH -> f up to 19.5 MHz; 1/4 in copper tubing; 6 cm dia primary over 4 cm dia secondary; interchangeable primaries set couplingSource quote & editorial note
the Dee may be oscillated with voltage amplitudes of up to approximately 3000V relative to the grounded Dummy Dee. The Dee capacitance is approximately 76 pF. The secondary coil inductance of 0.87 uH or more in parallel with the Dee capacitance yields a resonance as high at 19.5 MHz, which is the maximum cyclotron frequency corresponding to 411 keV protons in the maximum magnetic field of 1.28 T. ... These inductors are 1/4 inch copper tubing, wound coaxially, with the 6 cm diameter primary coil outside the 4 cm diameter secondary coil. The inductance of the primary coil can be changed by replacing the coil with one having a different number of turns, several of which have been constructed
Editorial note, tabletop extrapolation: Concrete worked values at the same scale, but measure your own machine's total capacitance (dee + stray + coil) and size the coil from L = 1/((2*pi*f)^2 * C_total); the swappable-primary approach lets you retune coupling without rebuilding the tank. The 411 keV is that machine's figure at its own field and extraction radius.
-
Watch coil insulation temperature: the coil manufacturer's table halves expected insulation life roughly every 8 C (8-40 years at 79 C, 4-20 at 87 C) with 130 C the maximum allowable; ORNL alarmed at 70-80 C, and coils take 1-3 hours to reach thermal equilibrium.
life ~ halves per ~8 C and 130 C max allowable (manufacturer's table, this coil); alarm 70-80 C; t_equilibrium ~ 1-3 hSource quote & editorial note
An alarm warns the operator when the coil temperature has reached a predetermined value, usually 70 to 80 C ... one to three hours are required for the temperature to reach equilibrium ... the maximum life of the magnet coil insulation, which the manufacturer estimates will vary with temperature as follows: [table: 79 C, 8-40 years; 87 C, 4-20 years; ... 130 C maximum allowable]
Livingston & Boch, The Oak Ridge 86-Inch Cyclotron — ORNL-1196, OSTI 4357145 (1952) — p. 33
Editorial note, tabletop extrapolation: Directly applicable: put a thermocouple in the next machine's winding and log it; a coil that is fine at 30 minutes can still cook at 2 hours. The 130 C figure is this manufacturer's rating for this insulation - a next machine's ceiling is its own insulation's thermal class.
-
Put filter and tank inductors in the direct airstream of a cooling fan; coils outside the airflow run hot even when the semiconductors are fine.
Source quote & editorial note
It is important for the coils should be in the air stream of one of the cooling fans (they will run hot if not).
Buckler, Solid-State, 2-Decade, 1.25 kW Linear Amplifier — Development Notebook (2015) — p. 28
Editorial note, tabletop extrapolation: Applies to the homemade dee-tank coil: assess its RF loss and temperature under the intended loaded-Q and coupling conditions (resonator circulating current depends on Q and coupling, not on the DC feed), and give it forced air if it runs hot.
-
Do not put exposed nickel in a high-RF-current path: a nickel-plated 19 MHz copper-tube tank coil ran at 350 C (near nickel's Curie point) where the identical bare-copper coil ran at 65 C. A nickel underlay beneath chrome or silver is suspect unless the top conductive layer is continuous and several skin depths thick at the operating frequency.
ferromagnetic plating: delta shrinks with permeability; Ni (mu~500) delta = 0.00025 in at 1 MHz vs Cu 0.0025 inSource quote & editorial note
This operated normally at 65 C but when an identical coil, which had been nickel plated, was substituted, the operating temperature rose to 350 C.
Fowler, Radio Frequency Performance of Electroplated Finishes — Proc. IREE Australia (1970) — p. 4
Editorial note, tabletop extrapolation: Reject nickel-plated hardware anywhere RF current flows in the resonator, coil, or ground-return path unless the overplate is verified thick and continuous - or validate by measuring loss and temperature.
-
Specify electrical-grade copper for RF parts: common phosphorus-deoxidized copper tube (0.015-0.08% P) runs only 60-90% IACS conductivity, versus ~100-101% minimum for certified electrical grades (C11000/C10100).
P-deox Cu tube: 60-90% IACS; electrical grade: ~100-101% IACS min (certify, don't assume); Rs ~ 1/sqrt(sigma), so the conductivity gap is worth ~6-23% in RF surface resistanceSource quote & editorial note
Most commercially available copper tube contains 0.015% to 0.08% phosphorus as a de-oxidising agent, so that its conductivity may range from 60% to 90% I.A.C.S.
Fowler, Radio Frequency Performance of Electroplated Finishes — Proc. IREE Australia (1970) — p. 6
Editorial note, tabletop extrapolation: Buy the tank-coil tubing as electrolytic/electrical-grade (C10100/C11000) copper with certified conductivity, not generic plumbing tube - worth roughly 6-23% lower RF surface resistance depending on where the plumbing tube fell in its range.
-
Practical single-layer air-core coils typically reach true Q up to about 800; very few circuits need Q above 900, and designs much over 1000 usually force abnormal physical dimensions.
typical practical true Q up to ~800; Q much over ~1000 usually means abnormal dimensionsSource quote & editorial note
typically have true Q values of up to about 800. Very few practical circuits require a Q above 900. Attempting to design a coil with a True Q much over 1,000 usually results in a coil with abnormal physical dimensions
Murphy, The Elusive Q of Single-Layer Air-Core Coils — CQ Magazine, May 1999 (1999) — p. 1
Editorial note, tabletop extrapolation: Do not budget the resonant step-up on textbook thousands: measure or model the loaded Q of the actual resonator under representative coupling (loaded Q sits well below the coil's unloaded Q), then size the amplifier for 5-13 kV dees from that measurement.
-
Expect a Q meter to read below true coil Q: the instrument measures circuit Q, and the coil's distributed capacitance loads the reading down.
Q_measured < Q_true (distributed-capacitance error); circuit Q != coil QSource quote & editorial note
the presence of the coil's distributed capacity causes the Q observed by the Q meter to be lower than the true Q of the coil
Murphy, The Elusive Q of Single-Layer Air-Core Coils — CQ Magazine, May 1999 (1999) — p. 1
Editorial note, tabletop extrapolation: For the cited Q-meter method, treat the reading as a lower bound and keep leads and fixture capacitance minimal. A VNA measurement is a different animal: state whether loaded or unloaded Q is being extracted, calibrate and de-embed the fixture, and include the distributed capacitance in the fit - VNA errors can bias either direction.
-
Q increases with coil diameter and with frequency within the source's tested single-layer geometries, so for a given inductance at HF prefer the physically largest coil practical.
Q rises with dia (3-30 MHz charts: 1.0 in dia ~300-500 vs 4.0 in dia ~2000-3000) and with sqrt-like frequency dependenceSource quote & editorial note
Q increases with coil diameter (see figs. 1-4). Q increases with coil length, rapidly when the L/d ratio is small ... Q increases with frequency
Murphy, The Elusive Q of Single-Layer Air-Core Coils — CQ Magazine, May 1999 (1999) — p. 1-2
Editorial note, tabletop extrapolation: At 9 MHz a 3-4 inch diameter tank coil in the charted geometries reads Q over 1000. At fixed frequency and capacitance the dee voltage scales as sqrt(P*Q) - doubling Q at the same drive buys about 40% more voltage, not double - so treat Q gains as helpful, and verify with the loaded Q actually measured.
-
Wind single-layer HF coils with conductor diameter between 0.45 and 0.70 times the center-to-center turn spacing; the source notes not all commercial stock coils meet this condition.
0.45*S <= wire_dia <= 0.70*S (S = center-to-center turn spacing)Source quote & editorial note
The conductor diameter must be within the range of 0.45 and 0.70 times the center-to-center distance between adjacent turns (not all commercial stock coils meet this condition).
Murphy, The Elusive Q of Single-Layer Air-Core Coils — CQ Magazine, May 1999 (1999) — p. 2
Editorial note, tabletop extrapolation: For a 9 MHz matching/tank inductor, space the turns so the wire fills 45-70% of the pitch - close-winding bare tubing costs Q (proximity effect is the standard explanation, beyond this source's scope) - and check any stock coil against the ratio before trusting its rated Q.
-
Maximum Q occurs at a coil length-to-diameter ratio between about 0.35 and 0.45, decreasing rapidly below that ratio and more slowly above it - aim near the optimum band.
Q peaks at L/d ~ 0.35-0.45; falls fast below, slowly above - stay near the band, erring slightly long if forced off itSource quote & editorial note
Maximum Q occurs at a coil L/d ratio of between (depending on other coil design parameters) 0.35 and 0.45, decreasing rapidly below that ratio and more slowly above
Murphy, The Elusive Q of Single-Layer Air-Core Coils — CQ Magazine, May 1999 (1999) — p. 2-3
Editorial note, tabletop extrapolation: Make the resonator coil short and fat (length a bit under half its diameter), not the long skinny solenoid that fits most easily in a corner - and not a pancake either: below the optimum Q collapses quickly.
-
Do not trust simple coil design equations outside their validity range: L/d below 0.35, fewer than about 4 turns, or wire-to-spacing ratios outside 0.45-0.70.
Callender/Medhurst Q equations valid only for L/d >= 0.35, n >= ~4, 0.45 <= dia/S <= 0.70Source quote & editorial note
The equations do not hold for coils with a length-to-diameter ratio of less than 0.35:1, coils with less than about 4 turns, or coils with conductor diameter-to-turn spacing ratios of less than 0.45:1 or greater than 0.70:1.
Murphy, The Elusive Q of Single-Layer Air-Core Coils — CQ Magazine, May 1999 (1999) — p. 3
Editorial note, tabletop extrapolation: A 2-3 turn link or coupling loop at 9 MHz is outside the formulas; measure it rather than calculate it.
-
Size water-cooled copper main coils around the source's practically achievable engineering current density of ~5 A/mm^2 - defined there as ampere-turns over winding cross-section (superconducting NbTi windings reach 120-150 A/mm^2).
j_eng(Cu, water-cooled) ~ 5 A/mm^2; j_eng(NbTi SC winding) ~ 120-150 A/mm^2Source quote & editorial note
The practically achievable engineering current density (the ratio of the value of the ampere-turns in the winding to the cross section of the conductor) is of the order of 5 A/mm2.
Smirnov, The Cyclotron and Its Modeling — Phys. Part. Nuclei 52 (2021) — p. 15-16
Editorial note, tabletop extrapolation: First-cut sizing for a next machine's coil pack: NI / 5 A/mm^2 estimates the winding cross-section with water cooling - a starting point that still owes fill factor, cooling channels and insulation their space, and the thermal calculation is the real gate (magnet-power calculator). Air-cooled magnet wire derates well below this (dg-092).
-
Optimize coil height (and yoke/pole area ratio) by minimizing combined steel + copper + power cost; the cost minimum is flat, so deviating for mechanical convenience costs little.
minimize cost(steel) + cost(Cu) + cost(power) vs coil height and A_yoke/A_poleSource quote & editorial note
The coil height giving the minimum cost was found for a field of 20,000 gauss. Since the cost curve had a flat minimum this resulted in little increase in cost.
Creutz, Design and Construction of Synchro-Cyclotron — NYO-780 (1950) — p. 8
Editorial note, tabletop extrapolation: General magnet economics in FORM: minimize steel + copper + power cost for your own prices and expect a flattish minimum near the optimum - CIT's flatness belonged to a 20-kilogauss design at 1950s prices, so re-run the small optimization with today's numbers before leaning on the flatness for convenience deviations.
-
When welding cases or fittings around finished coil windings, mask every metal seam (CIT: glass tape) so weld flash cannot reach the insulation.
Source quote & editorial note
Glass tape is inserted along all metal seams to prevent weld-flash from entering the can.
Creutz, Design and Construction of Synchro-Cyclotron — NYO-780 (1950) — p. 14
Editorial note, tabletop extrapolation: Directly applicable craft rule for welding on or near a next machine's coil case: glass tape or an equivalent temporary barrier keeps weld flash and spatter out of the can. It does nothing against brazing flux, molten filler or conducted heat - hot work near a wound coil also needs thermal protection and temperature monitoring, or should be finished before winding. [Note revised 2026-08-23: earlier note extended the barrier to 'any welding or brazing'.]
-
In a mixed copper/aluminum/steel water loop, add a corrosion inhibitor: CIT found trace dissolved copper provoked attack on the aluminum and steel (their chromate dose is the report's recipe - re-read queued; chromate is restricted today regardless).
1/3 oz sodium chromate per gallon (historic; chromate now restricted)Source quote & editorial note
requires the addition of an inhibitor to reduce attack on the aluminum and steel provoked by the presence of minute quantities of copper in the water.
Creutz, Design and Construction of Synchro-Cyclotron — NYO-780 (1950) — p. 53
Editorial note, tabletop extrapolation: Directly applicable chemistry for any next machine's water loop touching Cu plus Al: pick a modern inhibitor for the actual alloy set, water chemistry and temperature - the transferable fact is that trace copper is the aggressor, so the loop needs treatment even when each metal alone would be fine.
-
Water-cool high-current terminals and fit them with thermal switches that trip the supply before the terminals overheat.
Source quote & editorial note
All the adapters on the coil terminals are water cooled and supplied with thermal switches to protect the coil terminals from overheating.
Creutz, Design and Construction of Synchro-Cyclotron — NYO-780 (1950) — p. 56
Editorial note, tabletop extrapolation: Directly applicable - thermal cutouts on a next machine's coil terminals/lugs (and dee stem cooling) are cheap insurance against a loose-joint meltdown.
-
Magnet iron grows steeply with pole diameter across the census: 16-in -> 6 tons Fe, 18-in -> 6, 27-in -> 10, 28-in -> 17, 31-in -> 31, Copenhagen 90-cm -> 35, Washington 54-in-core -> 70; copper or aluminum windings add 1-12 tons.
census tonnage vs pole diameter: growth is steep but not a clean power law - gap, yoke geometry and field vary across the setSource quote & editorial note
Weight, Fe 6 ; Cu 4 tons. Winding 3/4 in x 1/16 in strip.
Howard, Cyclotrons and High-Energy Accelerators, 1958 — ORNL-2644 (1958) — p. 106
Editorial note, tabletop extrapolation: Extrapolating down the census, an 8-in-pole machine sits in the fraction-of-a-ton class - hobby-crane scale, and the reference machine's 757 lb H-frame agrees - while every inch of added pole diameter on a next machine is bought with steeply growing steel.
-
Air-cooled magnet windings sufficed on documented small machines: the survey lists Stanford's 27-in (12.5 kG, 10 t Fe) and Howard's 16-in (15-16 kG) with air-cooled coils.
Source quote & editorial note
Air-cooled coils. Iron ore blocks for shielding
Howard, Cyclotrons and High-Energy Accelerators, 1958 — ORNL-2644 (1958) — p. 127
Editorial note, tabletop extrapolation: Precedent that air cooling can work at this scale - two real machines did - not proof that a given coil can: adequacy is set by I^2R dissipation, winding geometry, insulation rating, duty cycle and airflow. Do the dissipation arithmetic (magnet-power calculator) and monitor winding temperature (dg-220) instead of citing precedent.
-
Keep magnet coils as small as a reasonable power budget allows: coil resistance grows with mean circumference (the quote), and the steel circuit that must wrap around the coil grows with it - the report's steel-scaling expression accompanies the quoted argument (scan re-read queued).
R_coil ~ mean circumference; steel volume ~ (2*coil height + radial width); achieve small coils via high average conductivity (material, low temperature, high space factor)Source quote & editorial note
1. The resistance of the coil is proportional to its mean circumference. 2. An amount of steel approximately proportional to two times the height of one coil, plus the radial width of the coils, is required to complete the magnetic circuit.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. PDF p.25 = printed p.25 (TID-454, Sec. 1.2 Magnet Coils, 'Introduction')
Editorial note, tabletop extrapolation: The compounding is the point - on any H-frame rebuild, fat coils cost twice (copper AND the longer steel circuit around them), so invest in space factor and cooling before adding turns.
-
In the report's practice, a high-current low-voltage magnet coil needs insulation only to maintain mechanical separation of the conductors; the report pairs this with direct cooling through a few large channels in large conductors rather than many small ones.
Source quote & editorial note
In a high-current low-voltage coil, insulation is required only to maintain mechanical separation of the conductors.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 25
Editorial note, tabletop extrapolation: What transfers is the architecture - few turns of heavy conductor at high current, direct cooling through generous passages - which beats many-turn fine-wire coils on space factor and pumping pressure. The bare-minimum insulation standard does not transfer: a modern coil wants verified turn-to-turn and ground insulation against inductive transients (dg-218's dump events), abrasion, thermal aging and coolant exposure, cheap as modern materials make it.
-
When no large winding machine is available (winding on site), build the coil as a flat-wound helix of conductor pieces fabricated as annulus sectors and joined into a continuous helix, cooled by water tubes on the inner and/or outer circumference.
Source quote & editorial note
A second type of coil which is more attractive, when the coil must be wound at the cyclotron site, is a flat-wound helix.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 26
Editorial note, tabletop extrapolation: Directly a garage-scale construction technique: cut flat copper sectors, stack into a helix, join into a continuous conductor - no winding mandrel needed. The joints are the engineering: braze for permanent low-resistance splices, bolt only with designed contact pressure and area (the report's joint-sizing criterion: scan re-read queued for the number), and place cooling per the report's tube arrangement.
-
Choose coil proportions by minimizing total owning cost - the report optimizes the combined costs of steel, copper, and energy against the coil OD/ID ratio (its Eq. 114 and nomographs; details report-attributed, scan re-read queued for the equation and the 1952 unit costs).
minimize C(steel volume, copper volume, energy over machine life) over x = r_out/r_in; report's Eq. 114 with its 1952 unit costs - re-derive with current prices and audit dimensions first (one continuous watt for 10 years = 87.66 kWh before duty factor)Source quote & editorial note
The costs which are affected are the combined costs of steel, copper, and energy.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 30-32
Editorial note, tabletop extrapolation: This collection's only explicit dollar-optimization of magnet proportions: redo the sweep with 2026 unit costs (scrap steel, surplus copper, $/kWh over expected machine life and duty cycle) - after re-reading the source for the variable definitions, since a cost formula reused without its unit system is a trap. NYO-780 p.8 did the equivalent sweep by model.
-
Total magnet cost is a SLOWLY VARYING function of coil outside diameter near the minimum, so deliberately build the coils smaller than the computed optimum and buy operating convenience and gap access for almost nothing.
Source quote & editorial note
For operating convenience, the coils should be made smaller than is indicated because the total cost is a slowly varying function of the coil outside diameter near the minimum of cost.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 30
Editorial note, tabletop extrapolation: Licence to trade cost-optimality for access, cooling clearance, or stock material sizes - the optimum is a plateau, not a peak. How much plateau: evaluate the cost function at the smaller diameter and report the actual penalty rather than assuming it is a few percent. Same flat-minimum finding as NYO-780 p.8 (coil height); cite both.
-
The unit costs that drive magnet optimization could, in the source's judgment, only be truly determined after years of operation - so the first-pass optimization uses estimates, and refining it beyond the accuracy of those inputs is wasted effort.
Source quote & editorial note
It appears that the unit costs can only be determined after the cyclotron has been in operation for several years, so estimates must be employed.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 30
Editorial note, tabletop extrapolation: A 1952 statement of the plan's own doctrine, applied with modern tools: use estimated lifecycle costs with a sensitivity check on the uncertain inputs, update from quotations and commissioning actuals as they arrive, and avoid polishing the spreadsheet past its input accuracy.
-
Expect the analytically computed optimum coil OD/ID ratio to be biased HIGH - the source says its assumptions make the given x too large - and note the optimum is scale-dependent: do not copy another machine's coil proportions across a size class.
Source quote & editorial note
It is quite clear from either equation that this factor, optimum x, depends on scale factor. The assumptions made cause the value of x given by the equation to be too large.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 31
Editorial note, tabletop extrapolation: Two cautions in one: treat big-machine coil proportions (including TID-454's own x~1.4) as non-transferable to an 8-12 in machine, and rather than mechanically shaving the computed value, redo the optimization at the actual scale with a geometry-dependent field/cost model.
-
One square centimeter of TRUE metallic contact distributed over a coil joint carries 10,000 A with negligible resistance and temperature rise - the report's point being that electrical capacity is rarely the binding constraint once real contact is achieved, mechanical strength is.
~10 kA per cm2 of metallic contact with negligible drop; joint requirement ~ mechanical strengthSource quote & editorial note
One square centimeter of metallic contact distributed over the joint will carry 10,000 amps with negligible resistance and temperature rise.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 32
Editorial note, tabletop extrapolation: Bolted bus laps at amateur coil currents have huge nominal margin by this figure - but nominal lap area is not metallic contact area: oxide, pressure, fastener relaxation and thermal cycling decide the real contact. Prepare surfaces, clamp hard, lock against loosening, then verify with a four-wire millivolt-drop measurement and a full-current temperature check. A joint that passes those two tests is electrically invisible; one that hasn't been tested is a fire waiting for a loose bolt.
-
Match the DC supply to the magnet coil so that (maximum voltage)/(maximum current) equals the coil resistance; otherwise part of the supply's capability can never be delivered.
V_max/I_max = R_coil for full utilization of the supplySource quote & editorial note
The generator should match the coil in the sense that the quotient of the maximum voltage output and the maximum current should be equal to the resistance of the coil.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 33
Editorial note, tabletop extrapolation: When sizing a surplus supply for the next machine's coil - or the turn count for a given supply - pick turns so the coil's HOT resistance sits at the supply's V_max/I_max corner: copper rises 20-40% in resistance from cold, so a cold-matched coil starves at temperature. And confirm the supply can actually hold its corner continuously; not every surplus unit can.
-
For geometrically similar coils at fixed current density, field scales with linear size (h/(f*r0*j0) invariant, so H ~ r0), while power and conductor volume grow as r0^3; at fixed target field instead, power grows only ~linearly with r0.
h/(f*r0*j0) = design constant; at fixed j0: H ~ r0, P and V_conductor ~ r0^3; at fixed H: P ~ r0 (Eqs. 1-2)Source quote & editorial note
the field obtained is proportional to the inside radius of the coil and a high field can be obtained by increasing the scale ... the power p and the volume of conductor v increase with the cube of the inside radius.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 116
Editorial note, tabletop extrapolation: SCALE-SCOPED (megagauss-era context), and useful for estimating specific coils: it explains why small-bore air-core inserts and compact analyzing magnets are economically comfortable while large air-core fields carry punishing power bills - run the numbers for the actual coil rather than treating the scaling as a feasibility verdict.
-
Match design effort to field class: the source says power and maximum current density 'become important factors and more complicated designs are useful' for fields of 1e5 gauss and above - elaborate minimum-power current distributions (j ~ sin(theta)/r^2 kernels) are particularly motivated in that regime. [Corrected 2026-08-23: earlier text inverted this into a claim that near 1 kG air-core coil power is small and optimisation 'seldom worthwhile', which the quote does not say.]
ideal minimum-power distribution: j = k*sin(theta)/r^2 inside boundary r^2 = k'*sin(theta) (Eqs. 3-4) - relevant only in the high-field regimeSource quote & editorial note
For fields of 10^5 gauss and above, the situation is quite different; the power and maximum current density become important factors and more complicated designs are useful.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 122
Editorial note, tabletop extrapolation: Locates amateur work far below the exotic regime: for sub-kG correction coils, steering windings and test solenoids a simple winding is usually adequate - but 'usually' is earned by computing NI, resistance, I^2R heating, temperature rise and current density for every coil, since a small high-duty coil can be power-limited at any field. [Note revised 2026-08-23: earlier note said 'sophistication buys nothing'.]
-
For a uniform field from a split coil pair at high field, the source's criticism is that thin-winding Helmholtz sections (cross section small next to radius squared) require excessive power; its doctrine is to set uniformity by a power-series expansion of the mid-plane field, choosing coil boundaries to null low-order terms rather than simply making the coils huge.
expand H(u) in powers of u in the mid-plane (Eqs. 1-3) and null low-order derivative terms by choice of coil boundary; thick sections (cross section ~ a^2) for power economySource quote & editorial note
Helmholtz coils have cross sections small in comparison with their radii squared, and thus require excessive power where a high field is required.
Foss et al., Cyclotron Component Design Technical Reports — TID-454 (1952) — p. 108
Editorial note, tabletop extrapolation: The right doctrine for any air-core uniform-field fixture - probe-calibration coils, a beamline corrector, a small synchrotron's reference field: choose the winding section from the ampere-turns, resistance, I^2R and temperature-rise arithmetic, and reach for thick optimized sections when that arithmetic shows a power problem - a classic thin Helmholtz pair is fine where it doesn't.
-
Shift the beam center electrically with 'half-coils': an insulated conductor wrapped halfway around the pole piece, attached so the pole completes the circuit (the 600 A / 3.6 in / energy-sweep performance figures are the report's account - re-read queued).
600 A opposing half-coil set -> 0.5 oersted/in. gradient across an 86-in. poleSource quote & editorial note
One of these coils consists of an insulated conductor wrapped half-way around the magnet pole piece and attached so that the pole piece completes the circuit.
Editorial note, tabletop extrapolation: A field-trim knob that steers orbits without touching iron - as a modeling hypothesis for a next machine: specify ampere-turns and the return-current path, run the magnetostatic and orbit analyses (FEMM models it directly), check contact heating and forces, and only then test; variable-energy operation is a beam measurement away, not a feature to advertise from the wiring diagram.
-
Run beam-transport quads at deliberately low field (~1 kG): avoids iron saturation, keeps excitation power low enough to skip water cooling entirely, and leaves headroom; since lens strength parameter lambda scales as B^1/2 for a given particle and energy, excitation current is a smooth tuning knob.
B = (lambda/l)^2 * (a/2) * B_rho ~ 1 kilogauss at design point; lambda proportional to B^1/2Source quote & editorial note
This low field avoids saturation difficulties in the magnet iron and high excitation power requirements. Furthermore, it enables us to dispense with water cooling in the windings.
Editorial note, tabletop extrapolation: DIRECT: at a next machine's rigidity, transport-quad pole-tip fields of a few hundred gauss are plausible - compute the actual requirement from aperture, length and focal geometry (the formula) - and where field and current density land as low as the source's, unsaturated iron with air-cooled random-wound coils is exactly the regime they describe. Confirm with the dissipation arithmetic before skipping water (dg-708). OCR trap - the text layer renders the B^1/2 exponent as B^2; page image verified B^1/2.
-
Connect all four coils of a quadrupole strictly in series on one supply: paralleling (or individual supplies) brings 'extreme difficulty in maintaining uniform gradients' - the quoted reason. The report's winding specification, page-image verified: #22 heavy Formex magnet wire, ~3000 turns per coil in the 2.67 cm2 window (12,000 per unit), convenient maximum 500 mA and safe 625 mA at their 1000-circular-mil-per-ampere allowance, 72.5 ohms per coil at 20 C; ampere-turns sized by a path integral over the magnetic circuit (sum of l_i/mu_i terms) with margin - 5000 A-turns needed for 1 kG, designed for 6000.
series connection forces equal current through all four poles. NI by path integral over l_i/mu_i [the formula is handwritten in the source; its exact typography is partly illegible even at 600 dpi, but the prose defines l_i and mu_i, so the path-integral character is certain]; 1 kG needs NI = 5000, designed 6000; 3000 turns/coil #22, 72.5 ohm, 500-625 mASource quote & editorial note
A field of 1 kilogauss requires NI = 5000 ampere turns. As a safety factor, we have designed for 6000 ampere turns. ... Each coil will have exactly 3000 turns and the coils in each unit are connected in series
Bromley & Bruner, The Design of a Focusing and Analyzing System for the 27-inch Cyclotron Beam — NYO-3823 (1954) — p. PDF p.31 (printed page 28)
Editorial note, tabletop extrapolation: DIRECT wiring doctrine for any home-built multipole: gradient symmetry comes from forced equal current, not matched resistances - which is also why surplus-wire coil construction works, since the series circuit forgives resistance mismatch between coils.
-
First-pass excitation: NI = 2.02 x H(gauss) x gap(inches) for the air gap alone; in well-proportioned iron-return magnets the gap consumes 85-95 per cent of the total mmf, so take total NI ~ 1.15 x (NI)_gap as the starting approximation and let the model (or simulation) refine it.
(NI)_g = 2.02 * H[G] * l_g[in]; NI_total ~ 1.15 * (NI)_gSource quote & editorial note
the quantity (NI)g represents 85 to 95 per cent of the total mmf required (i.e., the efficiency ranges from 85 to 95 per cent), and Eq. 7 can be used to give a useful first approximation
Editorial note, tabletop extrapolation: The same arithmetic every H-frame designer runs today (Wouters and Zickler's CAS notes corroborate the sizing). The 85-95% efficiency band is the source's result for WELL-PROPORTIONED iron-return magnets: use it as a sanity check on FEMM excitation for a magnet in that class, and expect worse from lean yokes, corners, or parasitic joint gaps (dg-128).
-
The product of coil power and conductor weight is a design invariant set by ampere-turns and coil size: P x W_c = 0.118 x (NI/10^5)^2 x (mean turn length, in.)^2 for copper (0.131 for silver, 40 C mean). Choose the P/W_c split afterwards from cooling or cost — it fixes current density via J[A/in^2] = 486 x sqrt(kW/ton) for Cu.
P[kW] * W_c[tons] = 0.118 * (NI/1e6)^2 * (mean turn length, in.)^2 for copper (0.131 silver, 40 C mean) - the 0.118 rides with MEGA-ampere-turns squared and length squared (cf. dg-212); J = 486*sqrt(P/W_c)Source quote & editorial note
the product of the power and weight of a coil conductor depends on the ampere turns and the mean diameter of the coil.
Editorial note, tabletop extrapolation: The cleanest statement in this collection of the copper-vs-power trade: double the copper, halve the dissipation, at fixed NI. Lets a coil be resized on one line when a surplus supply or a heat limit is the binding constraint.
-
Continuous-duty current-density ceilings from calutron practice: ~1600 A/in^2 (2.5 A/mm^2) is the upper limit for oil-cooled coils, ~1000 A/in^2 (1.55 A/mm^2) for open bus bar in free convection; the project's economic balance point P/W_c ~ 5 corresponded to ~1050 A/in^2. Careful cooling design is what buys anything higher.
J_max ~ 1600 A/in^2 oil-cooled continuous; ~1000 A/in^2 free-convection busSource quote & editorial note
For continuous operation, 1600 amp/sq in. is about the upper limit used for oil-cooled coils. This compares with 1000 amp/ sq in. for open bus bars cooled by free convection
Editorial note, tabletop extrapolation: Brackets modern air-cooled small-magnet guidance from the 1940s operating side - mapped to the right geometry: the 2.5 A/mm^2 was for OIL-cooled calutron coils, and the 1.55 A/mm^2 for open bus bar with free-convection area a wound coil does not have. A passively cooled wound tabletop coil therefore belongs below both, in the ~1 A/mm^2 territory of the coil rules (dg-092), unless its own thermal test justifies more.
-
Coil space factor (copper volume over coil-container volume) came out 0.37 and 0.30 on two experimental models forced to use available conductor sizes rather than purpose-designed ones - the quote; the report's expectation for designed conductor is its surrounding discussion (scan re-read queued).
space factor ~ 0.5 designed; 0.30-0.37 with off-the-shelf conductorSource quote & editorial note
Two experimental models had values of 0.37 and 0.30, but in both cases it was necessary to use conductor sizes which were available but not specifically designed for the job.
Editorial note, tabletop extrapolation: Amateur coils are usually wound from whatever magnet wire is available: budget a pessimistic 0.3-0.4 space factor when sizing the coil window, and read handbook ~0.5 figures as purpose-designed-conductor numbers.
-
Working force formulas from the report's engineering pages (English units): pull between pole faces F[lb] = (kG)^2 x area[in^2] / 1.735 (the quoted line); its companion values give conductor force F[lb] = kG x amp x length[in] / 1750 and a copper strip hot-spot check dT[C] = 0.0094e-6 x width^2 x J^2.
F_pole[lb]=kG^2*A[in^2]/1.735; F_cond[lb]=kG*I*l[in]/1750; dT_Cu=0.0094e-6*w^2*J^2 [2026-09-06 re-read: the page prints the heating constant's multiplier as a bare 10^6 with no minus sign, while its resistivity rows print 10^-6 clearly; dimensional check requires e-6 - an original typo, page-image verified. The 1.735 pole-force constant checks against B^2/2mu0 to 1%.]Source quote & editorial note
Force on conductor (lb) = 1/1750 X kilogauss X amp X length (in.) Force between pole faces (lb) = 1/1.735 X (kilogauss)^2 X area (sq in.) Heating at center of conductor, degC = 0.00940 (Cu) / 0.00821 (Ag) X 10^6 X (inches of width of conductor)^2 X (amp/sq in.)^2
Wakerling & Guthrie (eds.), Magnets and Magnetic Measuring Techniques — TID-5215, Radiation Laboratory, University of California (1949) — p. PDF 31 (printed p. 21), Table 1.1 'Magnet Design Data', TID-5215 Vol. 1
Editorial note, tabletop extrapolation: The 1.735 pole-force constant is the imperial twin of B^2/2mu0 and matches it to 1%; the hot-spot width formula is a one-line check before winding wide flat strip on a driver-amplifier-fed coil.
-
Find end-cell compensation empirically: end coils adjacent to a yoke nominally need 50 per cent of a full coil, but yoke reluctance leaves the end gaps low - Alpha II measured 4.0 per cent low at the 50% setting, and practice converged on higher end-coil ratios settled by measurement, so BUILD IN TAPS (the intermediate measurements and other machines' ratios are the report's data - scan re-read queued).
measure end-gap deficit at two end-coil turn ratios; extrapolate linearly to zero deficitSource quote & editorial note
It was found that when the number of turns on the end coils was 50 per cent of a full coil, the field in tanks adjacent to the yokes was 4.0 per cent low.
Editorial note, tabletop extrapolation: The pattern transfers to any edge-compensation knob - outer-radius shim thickness, trim turns near a yoke window, correction-coil ampere-turns: measure the deficit at two settings, extrapolate linearly to zero as the FIRST estimate, then confirm with a third measurement - saturation and coupling bend the response, so one iteration is the hope, not the promise.
-
Support model (and real) coils against magnetic forces, not just gravity: UW's model coils, cooled by direct water contact "at the expense of structural support," were distorted when the supporting structure failed "presumably under the magnetic forces," developing shorted turns that dropped the field ~20% below the Rowland-ring prediction. Recovery expedient worth knowing: adding steel around the outer face of the yoke raised the gap field to its proper value "without affecting its shape appreciably."
Source quote & editorial note
the supporting structure for the coils failed, presumably under the magnetic forces. The coils became distorted and short circuits developed.
Editorial note, tabletop extrapolation: DIRECT at any scale: coil-on-coil and coil-on-iron forces scale with NI and B and have crushed amateur windings - brace windings as if they will be pushed, not just held up. (The outer return-path steel in UW's recovery is that machine's expedient; whether added steel raises gap field depends on where the circuit's reluctance actually sits - FEMM answers it.)
-
COLUMBUS's practice for its borrowed laboratory magnet: run continuously at no more than half the MAXIMUM coil current to avoid overloading it, and pick the operating field where the data-sheet homogeneity is best rather than where the field is highest.
Source quote & editorial note
Um den Magneten nicht zu überlasten, sollte er im Dauerbetrieb höchstens mit der Hälfte des maximalen Spulenstroms betrieben werden [tr.: run at no more than half the maximum coil current in continuous duty]
Editorial note, tabletop extrapolation: For any other borrowed or surplus magnet, use its actual continuous-duty specification (maximum and continuous ratings differ) and verify winding temperature under your duty cycle - half-of-maximum is this book's conservative default when no continuous rating is known. The choose-field-by-homogeneity move transfers as stated; record the chosen point as a thermal/homogeneity compromise, not a hard limit.
-
Water-cool a kW-class laboratory magnet with a closed loop, as COLUMBUS's student-built system does: a central-heating circulator providing ~10 l/min, an expansion vessel holding ~1 bar operating pressure, and a cooling-failure interlock that switches the magnet off via an emergency switch.
Source quote & editorial note
Im Betrieb müssen die Spulen des Magneten mit Wasser gekühlt werden. Dies geschieht durch ein (von Schülern selbst entwickeltes) Kühlsystem, das mit Hilfe einer Heizungspumpe für den notwendigen Durchfluss von ca. 10 l/min sorgt. Ein Druckausgleichsgefäß stellt den notwendigen Betriebsdruck von ca. 1 bar während des Betriebs her. Sollte das Kühlsystem einmal ausfallen, so wird der Magnet über einen Notschalter abgeschaltet. [tr.: in operation the magnet coils must be water-cooled, by a student-built cooling system whose central-heating circulator provides the necessary ~10 l/min flow; an expansion vessel maintains the ~1 bar operating pressure; should the cooling fail, the magnet is switched off by an emergency switch]
Editorial note, tabletop extrapolation: Size cooling from the measured coil loss, allowable winding temperature and coolant temperature rise - the 10 l/min is this magnet's number. A fail-safe interlock (flow AND winding temperature, arranged so failure trips rather than merely alarms) is cheap against a coil rewind; whether an air-cooled coil set needs duty cycling depends on its thermal design, not its power class.
-
Data-sheet benchmark for a surplus laboratory electromagnet of the class suited to a few-keV teaching cyclotron (per the reproduced Bruker BE-15 table - bitmap, not text-verifiable): 150 mm pole diameter, 5-100 mm adjustable gap, 430 kg, 2 x 800 turns at ~1.4 ohm per coil. Consistent series-connection operating points: 20 A gives 32 kAT and ~1.1 kW (cold); 15 A gives 24 kAT and ~0.6 kW; the book reads 300-400 mT off its chart at its operating current with the 75 mm gap.
series coils: NI = 1600*I; P = I^2*(2*1.4 ohm) cold. Ideal gap-MMF lower bound: B*g/mu0 = 22 kAT for 370 mT across 75 mm - a floor, real magnets need more; the chart, not the formula, is the datumSource quote & editorial note
Aus dem Diagramm 5.1 liest man für diesen Strom einen Wert zwischen 300–400 mT für die Flussdichte ab [tr.: for this current one reads 300-400 mT off Chart 5.1]
Editorial note, tabletop extrapolation: A home H-frame with 20 cm poles and a 3 cm gap reaches ~0.6 T with 15-20 kAT, so this surplus-magnet class is a legitimate alternative to winding your own - check the actual coil topology (series vs parallel feeds change the current arithmetic) and take B from a measurement or the manufacturer's chart at YOUR gap.
-
Coil-winding scale datum for a small cyclotron magnet built by hand, approximately 8 km of 13-gauge copper wire wound on six-inch (15.2 cm) pole pieces (El Cerrito, reported built 1947 by high-school students).
Source quote & editorial note
Approximately 8 kilometers of 13 gauge copper wire were wound around the six inch pole pieces for the electromagnet.
Cressman, The Design and Construction of a Small Cyclotron — Houghton College thesis (2006) — p. 15
Editorial note, tabletop extrapolation: A concrete scale anchor - kilometre-class wire on a hand-wound magnet is real, with the resistance and cooling that implies - but budget a NEW magnet from its own ampere-turn requirement, winding window, current density and duty cycle; pole diameter alone doesn't set wire length.
-
Cooling and protection budget for a 1.1 T-class magnet plus diffusion pump on one small chiller (3.8 L/min at 20 C total), 3 L/min to the magnet at 50 A (6 L/min would be needed at the 70 A rating) and 0.75 L/min to the diffusion pump, with an interlock that powers down the magnet below 2.5 L/min of flow or above 50 C on any coil.
Source quote & editorial note
an interlock which shuts down the magnetic if less than 2.5 liters per minute of chilled water are supplied
Cressman, The Design and Construction of a Small Cyclotron — Houghton College thesis (2006) — p. 36
Editorial note, tabletop extrapolation: The transferable pattern is the method, not the numbers: independent low-flow and over-temperature interlocks wired to POWER DOWN the load, with trip points derived from the coil's insulation limits or measured thermal performance (including sensor lag) - Houghton's 2.5 L/min floor and their coil ceiling are that machine's settings, not defaults.
-
Scrapyard magnet construction on Niell's machine: the yoke was soft iron scrap, the pole pieces 11.4 cm steel round stock wound with 13.5-gauge wire.
Source quote & editorial note
The magnet yoke was soft iron scrap, and the pole pieces were 11.4 cm steel round stock which were then wound with 13.5 gauge wire.
Cressman, The Design and Construction of a Small Cyclotron — Houghton College thesis (2006) — p. 16
Editorial note, tabletop extrapolation: A documented precedent that scrap return-path iron plus machined round-stock poles can serve a small machine - the machine as a whole made beam, though the survey doesn't isolate the magnet's contribution. For a new build, characterize candidate scrap (saturation, consistency, joints) and remember the return path needs cross-section, not pedigree.
-
A hybrid dipole architecture assigns each field-control function its own hardware layer: Sm2Co17 permanent magnets supply the main field for free, a copper trim coil gives fine adjustment over a limited range, movable outer iron plates give coarse adjustment, and NiFe alloy plates passively stabilize against temperature - power consumption falls far below an equivalent electromagnet while keeping operational tunability.
Source quote & editorial note
A typical hybrid dipole magnet (Fig. 1) consists of DT4E poles, yokes, Sm₂Co₁₇ permanent magnet blocks, a copper trim coil, outer tuning plates, NiFe alloy plates, and aluminum structural parts. In this configuration, the PM blocks provide the main magnetic field, while the trim coil allows for fine adjustment of the field strength within a limited range. This design significantly reduces power consumption compared to traditional electromagnets, while still preserving operational flexibility. To improve adaptability, an outer iron plate mechanism is incorporated for coarse field tuning ... to address the negative temperature coefficient of permanent magnets, NiFe alloy plates are placed near the magnet poles. These act as passive compensators to stabilize the magnetic field against temperature variations
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: a small PM-based magnet need not be untunable — layering a modest trim coil and a movable iron shunt onto a PM circuit restores fine and coarse adjustment within a limited range (±1.25% fine on this prototype) at a small fraction of an electromagnet's power. Enough for drift, matching and calibration; not the wide excitation range of a full coil.
-
Trim-coil sizing datum from the NSRRC hybrid dipole prototype: a 42-turn coil of 2 x 3 mm2 copper wire changes the integrated field by about 0.086% per ampere, and the source states a plus-or-minus 15 A range adjusts the field by approximately plus-or-minus 1.25% (its rounded endpoint) on a 0.75 T-class PM main field.
Source quote & editorial note
The trim coil is made of 2 × 3 mm2 copper wire and contains 42 turns ... The integrated magnetic field increases by approximately 0.086% for every 1 A of coil current (Fig. 4). With a coil current range of ±15 A, the magnetic field can be adjusted by approximately ±1.25%
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: a prototype calibration datum, not a scaling law — coil authority depends on gap reluctance, yoke geometry, saturation and coil placement, so compute or measure d(BL)/dI for the actual circuit. Percent-level trim on a PM-driven iron circuit is the right order for covering temperature drift; whether it also covers assembly tolerance needs a tolerance budget, not an assumption.
-
Coil electrical design point for the IUAC 1.2 T / 51 mm gap magnet (tender specification; the table's 'Operating Current' is a design rating — the machine has no beam yet) — total magnetizing force 64800 ampere-turns from two coils of 162 turns each at 200 A, wound from 10 mm x 10 mm hollow OFHC copper (ASTM C10200) with 6 mm water bore; per the same table, one coil is about 0.05 ohm and uses about 214.5 m of conductor weighing about 135 kg, the pair runs at roughly 20 V, and I²R from the tabulated values is about 2 kW per coil.
NI = 64800 A-turns (two coils, 162 turns/coil x 200 A) for B = 1.2 T, g = 51 mmSource quote & editorial note
[Coil Data table:] Total Magnetizing force (for two coils) — 64800 Ampere-Turns; No. of coils — 02 (Top and bottom); No of turns per coil — 162; Conductor size — 10 mm x 10mm x 6 mm diameter bore (OF-OK oxygen free copper grade ASTM C10200); Operating Current — 200 A; Approximate total length of one coil — 214.5 m; Approximate weight of one coil — 135 Kg; Approximate resistance per coil — 0.05 Ohm; Approximate operating voltage (for two coils) — 20 V
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: a complete, self-consistent coil design point (ampere-turns, turns, current, conductor, resistance, voltage, mass) published with enough detail to scale from — sitting just above the 0.6-1 T fields most amateur machines run. The low-voltage high-current choice (about 20 V at 200 A for ~4 kW total) shows a water-cooled hollow-conductor solution where amateur designs often accept hotter air-cooled solid-wire coils; scaling it needs the magnetic-circuit, thermal, ampacity and hydraulic calculations redone for the new geometry.
-
Coil cooling design limits specified for the IUAC magnet — low-conductivity water at 6 bar inlet and 20 C nominal, flow velocity below 3 m/s in the conductor bore, pressure drop below 4 bar (the spec table states the 4-bar limit per double pancake), coil temperature rise limited to under 40 C with thermal cut-off switches on the coil terminals, and every pancake's water connected to SS304/SS316 supply/return manifolds through non-conducting tube rated at least 12 bar at 100 C.
Source quote & editorial note
[Coil Data table:] Cooling type — Low conductivity Water cooled; Inlet cooling water pressure — 6 bar; Max Pressure drop per double pancake — 4; Water inlet temperature — 20°C (Nominal) ... Design parameters for cooling of magnet coils: Limiting value of temperature rise (deg T) of magnet coils < 40 oC; Velocity of flow in magnet coils < 3 m/sec; Pressure-drop (delta P) in magnet coils < 4 bar ... All pancake terminal water connections shall be connected with respective manifolds via proper non-conducting tube with proper pressure and temperature rating. The connectors and tubes shall have a working pressure rating at least 12 bar @ 100 oC
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: the working hydraulic design values for hollow-conductor magnet coils at the few-kW scale — one professional data point, not universal limits. The transferable method: parallel the water at the pancake level while the electrical circuit stays in series, and compute flow, pressure drop, temperature rise and water chemistry for the actual bore and length; every wetted component carries a pressure/temperature rating with margin (12 bar at 100 C here).
-
Coil winding and insulation practice specified for the IUAC magnet coils — no conductor joint is allowed inside a pancake; the conductor is wrapped with unvarnished electrical glass-fibre tape at 50 percent overlap giving about 0.5 mm turn-to-turn insulation; inter-pancake and terminal connections are silver-brazed (filler at least 40 percent silver); connectors between pancakes must carry at least 150 percent, and coil-to-coil / power-supply connectors at least 200 percent, of maximum current without significant heating; the finished coil is vacuum epoxy-impregnated to thermal class F (155 C).
Source quote & editorial note
No joint in the conductor is allowed inside a pancake ... The conductor shall be wrapped with glass tape with 50% overlap to produce approximate insulation thickness of 0.5 mm turn to turn ... Electrical connections between pancakes shall be made by brazing of proper copper connectors that can carry at least 150 % of maximum current without significant heating ... The electrical connectors and bus bar (or flexible cable) that will be used for connecting two coils shall be designed and made to conduct at least 200 % of maximum current without significant heating ... brazed using silver brazing filler (at least 40% silver) ... All the water-cooled coils of magnets will be inter-turn insulated with glass tape followed by epoxy-resin impregnation & encapsulation under vacuum. The thermal class of insulation is F Class (155 oC).
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: a compact recipe for building reliable water-cooled magnet coils — joint placement, tape overlap, brazing alloy, connector qualification and vacuum potting — from a lab that must warranty the result. The 150/200-percent connector requirements are current-carrying thermal criteria (carry the current without significant heating), not dimensional oversizing; the no-joints-inside-a-pancake rule and those qualification margins are cheap insurance for any coil builder.
-
Coil hydraulic quality-control tests specified before epoxy casting of the IUAC coils — the cooling passage of every pancake must pass a steel ball of at least 5 mm diameter and be documented; the vendor compliance sheet additionally requires in-house hydrostatic testing at 30 bar and hydrodynamic testing at 8 bar of the coil water circuits.
Source quote & editorial note
Before epoxy cast/after brazing water connectors with the pancake terminals, cooling passage of each pancake shall be tested passing with at least 5 mm diameter steel ball and documented ... [vendor compliance sheet:] Whether Bidder have Inhouse — 1. Hydrostatic Test @30 [bar] ... 2. Hydrodynamic Test @8 [bar]
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: the steel-ball pass test is a zero-instrumentation way to prove a hollow-conductor bore was not crushed or blocked during winding — exactly the failure an amateur winding fixture is most likely to cause — and the source runs it before potting because epoxy makes any blockage permanent. A ball pass shows minimum clearance only; pair it with a measured flow/pressure-drop check, and derive any pressure test from the ratings of the actual fittings rather than copying the vendor-sheet values.
-
Coil electrical acceptance tests specified for the IUAC magnet — insulation resistance measured between coil terminals and mandrel at a minimum of 1 kV DC, plus a hi-pot leakage test of the main coils at 1 kV DC held for one minute with less than 1 microampere leakage to the yoke; coil resistance and inductance are measured with a micro-ohmmeter bridge at uniform room temperature and recorded.
Source quote & editorial note
Insulation resistance testing: The insulation resistance between the coil terminals and mandrel using minimum voltage of 1kV DC shall be measured and noted. Insulation leakage current testing (HiPot Testing): DC voltage of 1 kV shall be applied between coil terminals and mandrel for one minute and the leakage current shall be recorded. The main coils shall be hi-pot tested at 1 kV DC for 1 minute, and it should have less than 1µA leakage to the yoke ... Coil resistance and inductance measurements shall be made with a micro-ohmmeter resistance bridge at room temperature, with the coil temperature uniform throughout and steady state conditions prevailing.
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: concrete pass/fail numbers for magnet-coil insulation testing — 1 kV, one minute, under 1 microampere — as one lab's acceptance criteria. The method transfers; the voltage does not automatically: select proof voltage from the coil's working voltage, insulation system and an applicable standard, and treat any hipot test as hazardous work — current-limited rated equipment, guarded connections, controlled ramp and dwell, and discharge before touching. Run it before the coil is bolted into an expensive yoke.
-
Radiation-environment design assumption stated in the IUAC coil epoxy specification — the coils are treated as sitting in a high ionization radiation area with a total absorbed dose of approximately 2 MGy over a 10-year operating lifetime, and the casting epoxy must be shown (by manufacturer dose-rate data sheet, approved before use) to sustain that dose.
Source quote & editorial note
The coils will work in high ionization radiation area. Total absorbed dose in coil shall be approximately 2 MGy in its lifetime of 10 years of operation. Epoxy resin should be able to sustain the above mentioned radiation dose. Technical data sheet of radiation dose rate for the offered epoxy should be provided to IUAC.
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: a rare explicit statement of the radiation dose a design team budgets for organic insulation next to an MeV-class cyclotron gap over a decade of teaching use. Long-lived small machines should treat coil insulation as a radiation-exposed component, not just a thermal one — and note a manufacturer dose-rate data sheet alone is thin qualification: survival depends on total dose, species, dose rate, atmosphere and the property retained, so prefer total-ionizing-dose test data for the actual resin.
-
Thermal protection scheme specified for the IUAC magnet coils — eight temperature sensors mounted per coil (the spec table prints the cut-off as '> 400 C' where 40.0 C is meant — its own text sets the switches at 40 +/- 5 C), fully insulated screw-on thermal cut-off switches on the return water lead of each pancake, and overload/high-temperature interlocks that shut off the magnet power supply.
Source quote & editorial note
Thermal cut-off switches (fully insulated in a screw on housing type), set to open an electrical circuit at 40°±5°C shall be fitted on the external lead (return lead of water circuit) of each pancake ... Suitable thermal switches will be placed on outer terminals of the coils to prevent over-heating of the coils (cut-off value: > 40 oC) by shutting off the power supply ... [spec table:] Thermal sensors (cut-off value) — > 400 C (8 nos. of sensors to be mounted on each coil); Interlocks — overload, high temperature cut-off
Editorial note, tabletop extrapolation: Editorial note, tabletop extrapolation: hardware thermal switches on every pancake's return water lead, dropping the supply through an interlock, is a simple, software-free protection pattern for a water-cooled coil stack — with two cautions. An outlet-mounted switch lags stagnant-water and winding hot spots when flow is lost, so pair it with flow or pressure detection; and the interlock must command the supply's controlled shutdown or energy-dump path, never break magnet current mechanically — an inductive circuit interrupted dry arcs.
-
Cable-related HV failure on the Rutgers 12-inch deflector: the run from the current-limiting resistor to the chamber used portable x-ray machine "Mammoflex" coaxial cable rated for 60 kV with a capacitance of 56 pF per foot; at around 30 kV, internal chamber arcing was accompanied by external arcing from the shield of the 6 foot cable segment to chassis ground, and one such arc terminated on the upper magnet coil, causing permanent damage to the magnet power supply requiring costly repair (the memo prints "the magnet power permanent damage"; the companion Cyclotrons 2013 paper states the magnet power supply). The stored energy in the 6 foot cable at 30 kV is given as about 0.2 Joules against a rule-of-thumb damage threshold of 1 Joule, with the note that the focusing influence of the magnetic field can enhance discharge damage.
Source quote & editorial note
The Mammoflex cable is rated for 60 kV and had a capacitance of 56 pF per foot. After installation of the new supply and cable, mysterious behavior was noticed and is still not fully explained. At sufficiently high voltages (~ 30kV) arcing inside the chamber occurred – both light and audible snapping were observed. Coincident with the internal arcing, external arcing was observed between the shield of the Mammoflex cable (of the 6 foot segment between the resistor and chamber) and chassis ground, such as the magnet frame. One such arc terminated on the upper magnet coil, causing the magnet power permanent damage, requiring costly repair. The stored energy in the 6 foot cable at 30 kV is about 0.2 Joules, not much lower than the rule-of-thumb damage threshold of 1 Joule. It is also known that the focusing influence of the magnetic field can enhance the damage of an electrical discharge.
Editorial note, tabletop extrapolation: The most expensive lesson in the document, and it scales down unchanged: HV cable capacitance is a stored-energy reservoir whose shield is not automatically at ground everywhere. Computing from the paper's own numbers, 56 pF/ft × 6 ft = 336 pF, and ½CV² at 30 kV is 0.15 J — the source's "about 0.2 J" at the same order (computed here). Neither 0.2 J nor the 1 J rule of thumb is a safety boundary; cable length is the variable a builder controls directly.
-
Radial Bz scans of the Rutgers 12-inch tapered pole tips at three excitations produced linear fits of y = -0.0025x + 0.7587 (R2 = 0.9862) at 20 A, y = -0.0033x + 1.029 (R2 = 0.9846) at 30 A, and y = -0.0039x + 1.1624 (R2 = 0.9846) at 40 A, with x in inches and y in tesla — 0.271 T gained from 20 to 30 A but only 0.133 T from 30 to 40 A, showing iron saturation.
Bz(r) [T] = 1.1624 - 0.0039 r[in] at 40 A; 1.029 - 0.0033 r at 30 A; 0.7587 - 0.0025 r at 20 ASource quote & editorial note
Linear Fit to Tapered Pole Tips' B-field at 3 Coil Currents ... y = -0.0039x + 1.1624 R² = 0.9846 ... y = -0.0033x + 1.029 R² = 0.9846 ... y = -0.0025x + 0.7587 R² = 0.9862 ... Fig.1 Radial measurements at three different magnet currents: 20, 30, & 40A
Editorial note, tabletop extrapolation: Hard numbers for a real 12-inch H-frame's excitation curve: about 0.76 T at 20 A, 1.03 T at 30 A, 1.16 T at 40 A — the tesla-per-amp halving between steps (0.0271 vs 0.0133 T/A) is THIS iron's saturation announcing itself. Computed honestly with P = I²R at fixed resistance: the 30→40 A step buys its 0.133 T at about 2.85× the incremental copper power per tesla of the 20→30 A step (700R/0.133 versus 500R/0.271). The fit slope is the normalized radial FIELD gradient, about −0.34% of central field per inch at 40 A — not the physical pole-taper angle. Where another magnet's payback ends is its own B(i) curve's business. (Fit values and R² read from the rendered Fig. 1; the 20/30/40 A assignment follows the curve intercepts, since the printed legend order is 30, 20, 40.)
-
The Rutgers 12-inch magnet coils came from a surplus source with unknown construction, so the Poisson/Superfish current density was set empirically until the model reproduced the measured peak 1.22 T at gap centre; that corresponded to 30,000 ampere-turns, and comparing the model against the linear portion of the measured B(i) curve implied about 850 windings per coil.
Source quote & editorial note
The coil current density was empirically set. The construction of the actual 12-inch cyclotron coils is unknown, as the coils came from a surplus source. The current density was varied in PSF through several points, until the peak 1.22 Tesla was achieved in the center of the gap. This corresponded to a PSF setting of 30,000 Ampere-turns. ... A comparison of PSF’s output with the linear portion of the actual measured B(i) curve can yield insight into the construction of the coils, which was determined to be about 850 windings per coil.
Editorial note, tabletop extrapolation: A recoverable-datasheet method for surplus coils: fit a magnetostatics model's excitation until it reproduces the measured field, then read effective turns from matched ampere-turns over the linear region — N = (fitted A-turns)/I, with the per-coil-versus-total convention stated explicitly, which this memo leaves ambiguous: 30,000 A-turns over 850 turns implies ~35 A on a per-coil reading, while the document's stated ~32 A nominal (dg-1687) with 850 turns gives 27,200 — a bookkeeping tension to resolve on your own magnet, not an error to copy. The 850 turns is the inferred construction of THESE coils, not sizing guidance.
-
The Rutgers 12-inch Poisson/Superfish B(i) curve was linear all the way to 30,000 ampere-turns with no saturation, while the measured B(i) curve of the actual magnet clearly rolls over above roughly 30 A (about 1.0 T) and reaches only about 1.17 T at 50 A — a documented case of a 2-D magnetostatics model failing to reproduce the machine's real saturation knee.
Source quote & editorial note
Fig.6 PSF B(i) curve, note lack of saturation ... Fig.7 Actual measured B(i) curve
Editorial note, tabletop extrapolation: A cautionary pair at the target scale: the same 2-D model that matched the measured radial field SHAPE missed the excitation curve's saturation knee entirely — as run, evidently without material nonlinearity doing its job. The correct lesson is narrower than 'knees cannot be modeled': a nonlinear 2-D solve with a real B-H curve can capture saturation (3-D leakage it cannot), so give the code proper steel data, then validate BOTH B(i) and the field shape against measurement through the knee. (Measured curve endpoints — roll-over above ~0.03 kA, ~1.17 T at 0.05 kA — read from the rendered Fig. 7, whose x-axis is printed in kA.)
-
As a stated future plan (not an achievement) at the time of the 2013 conference, the Rutgers program had secured an H-frame 19-inch magnet — a General Electric magnet delivered to Rutgers in 1947 and run for 35 years for NMR research before storage — for a second-generation educational cyclotron; its coils were awaiting new copper windings.
Source quote & editorial note
The cyclotron facility has already secured an H-frame 19-inch magnet, a special General Electric magnet delivered to Rutgers in 1947 … and operated for 35 years for NMR research before retirement to storage.[13] Upon acquisition, the venerable magnet coils were in need of refurbishing and are currently awaiting new copper windings. … Future plans include the assembly of a second generation 19-inch educational cyclotron.
Editorial note, tabletop extrapolation: PDF p.5 = printed p.295. One documented acquisition route: a decommissioned 1947 GE NMR electromagnet, secured for a planned second-generation educational machine — with the coils needing refurbishment as part of the price. It also records the scale step this program judged worth taking from a proven 12-inch: 19 inches, not 30. Before buying any surplus magnet of that vintage, inspect winding insulation, cooling passages, resistance and field quality; rewinding is a real possibility, not a certainty. This was a plan in 2013; the paper reports no beam from the 19-inch machine.
-
On the Rutgers deflector, internal arcing was accompanied by mysterious external arcing between the grounded shield of the HV supply's coaxial cable and grounded surfaces such as the magnet frame; one such arc terminated on the upper magnet coil and caused costly damage to the magnet power supply.
Source quote & editorial note
One such arc terminated on the upper magnet coil, causing costly damage to the magnet power supply.
Editorial note, tabletop extrapolation: PDF p.3 = printed p.368. A concrete, expensive failure chain for anyone adding HV to an existing machine — and it is two-stage: the internal deflector discharge excited the charged cable (the Blumlein mechanism, dg-1826), and the resulting EXTERNAL arc terminated on the magnet coil and took out the magnet supply. The warning that transfers: HV transients couple into unrelated subsystems through cabling, grounds and stray capacitance, so an HV fault must be analyzed as a whole-machine event, not a deflector event.
-
The Rutgers 12-inch cyclotron's upper and lower magnet coils are independently energized so the median plane can be deliberately shifted for axial steering; while holding the average ampere-turns constant, coil currents of 17/12, 14.5/14.5 and 12/17 amps (top/bottom) all still brought beam to the chamber periphery.
Source quote & editorial note
The magnet’s upper and lower coils are independently energized for intentional field imbalance so as to shift the median plane. … Figure 6 shows three standard radial-draw beam images: the left frame top/bottom coil at 17/12 amps, the middle frame at 14.5/14.5 amps, and the right frame at 12/17 amps.
Editorial note, tabletop extrapolation: PDF p.3 = printed p.371 (design intent on PDF p.1 / printed p.369). A genuinely cheap axial-steering mechanism for a small machine: energize the two coils independently and trim the median plane. On this machine a 5 A top-to-bottom imbalance about the 14.5/14.5 A balance point still brought beam to the periphery — a demonstration that the knob has useful range, with transmission, centering and beam quality at each setting still to be measured on any machine that copies it.
-
Nine-inch cyclotron magnet electrical and cooling budget - the 1780 pound magnet needed 40 volts at 168 amps (7 kilowatts) for the 1.2 Tesla maximum, but only 28 volts at 114 amps (3.2 kW) at the 0.889 Tesla operating point; coil cooling water ran at approximately 38 PSI inlet pressure and no less than 4 GPM, regulated by an inline pressure regulator with an impeller-driven magnetic pick-up digital flow meter.
Source quote & editorial note
The magnet weighs 1780 pounds, it requires 40 volts at 168 amps, 7Kilowatts, to produce the maximum field of 1.2 Tesla. Only 28 volts at 114 amps, 3.2 kW, is required at the operating value of 0.889 Tesla. Water cooling is used to remove the heat generated by the coils, the inlet pressure is approximately 38 PSI and flow rate is no less than 4 GPM. The pressure is controlled with an inline pressure regulator and the flow rate is monitored with an impeller driven magnetic pick-up digital flow meter.
Editorial note, tabletop extrapolation: The most useful sizing datum in the document: backing off from 1.2 T to the 0.889 T operating point cut coil dissipation from 6.7 kW (40 V × 168 A; the author's "7Kilowatts" is rounding) to 3.19 kW — a factor of about 2.1 — while still requiring monitored water cooling (38 PSI, ≥4 GPM, flow meter). The shape of the lesson transfers (field costs quadratic-ish power near saturation; margin is cheap to buy by backing off), the numbers belong to this 1780-pound magnet.